Rockwell Automation Publication 2080-UM001B-EN-E - November 2011
IPID Function Block
This function block diagram shows the arguments in the IPIDCONTROLLER
function block.
The following table explains the arguments used in this function block.
IPIDCONTROLLER Arguments
Parameter
Parameter
Type
EN
Input
Process
Input
SetPoint
Input
Feedback
Input
Auto
Input
Initialize
Input
Gains
Input
IPIDCONTROLLER
IPIDCONTROLLER
ENO
EN
Output
Process
SetPoint
AbsoluteError
FeedBack
ATWarning
Auto
OutGains
Initialize
Gains
AutoTune
ATParameters
ErrorMode
Data Type Description
BOOL
Function block enable
When EN = TRUE, execute function.
When EN = FALSE, do not execute function.
Only applicable to LD, EN is not required in FBD
programming.
REAL
Process value, measured from the output of controlled
process.
REAL
Set point value for desired process
REAL
Feedback signal, measured from control input to a
process.
BOOL
Operating modes of PID controller:
• TRUE —controller runs in normal mode
• FALSE — controller out value equals to feedback
value
BOOL
A change in value (True to False or FALSE to TRUE)
causes the controller to eliminate any proportional
gain during that cycle. It Also initializes AutoTune
sequences.
GAIN_PID
Gains for IPIDCONTROLLER
See GAIN_PID Data type
C
Appendix
41