Explosion Protection - Pentair HLTSTAT10C Instruction Manual

Hazardous location heaters
Table of Contents

Advertisement

Manufacturer
CSA Certificate
CSA Type of Protection
IEC Scheme Certificate
EC Type Examination Certificate
Marking
INSTALLATION INSTRUCTIONS
The thermostat must be attached to the face of the heater as noted. Pentair DAHHL
finned heaters are equipped with slotted mounting rails in the fins. Slightly loosen the
mounting bolt included in the thermostat.
Insert the head of the bolt into one of the slotted mounting rails of the finned profile.
The PTFE spacer must remain outside, as this provides the right gap from the
thermostat to the surface of the heater fins. Carefully tighten the bolt by turning the
thermostat. DO NOT OVERTIGHTEN.
The thermostat is equipped with a ground terminal. Use a cable gland or a ½ NPT
conduit depending on the application.
Be careful not to bend or exert any load on the connection cable during unpacking and
transport.
Before entering the customer-supplied Ex junction box, the connection cable must be
firmly installed and mechanically protected observing the permissible bending radius of
5 times the outside cable diameter.
If the connection is made in a hazardous area, the connection cable must be connected
in a housing that meets the requirements of one of the types of ignition protection
mentioned in EN 50014 Section 1.2.
When determining the operating temperature, the maximum permissible ambient
temperature, self-heating and, possibly, heat transfer (medium) must be considered.
In dust hazardous areas, the applicable requirements of the EN 60079-14 have to be
observed.
CAUTION! Remove the RED protection cap only for ½ NPT conduit installation. Never
remove the adapter. See Figure 3 on page 6
The components must only be connected and secured by certified technical personnel
in accordance with the label specifications rated voltage and rated current. Circuit
breakers suitable for up to 16 A can be used for short circuit and line protection.
A ground terminal is provided for the purpose of ensuring potential equalization; see
Figure 1 on page 5. The terminal is marked as such.
- 4 -

EXPLOSION PROTECTION

© 2016 Pentair Equipment Protection
TAE
INTERTEC-Hess
1655545 (LR43674)
Cl. I, Grp. ABCD T6
Cl. II Grp. EFG
IECEx PTB 07.0054X
PTB 03 ATEX 1136 X
II 2 G Ex d IIC T6
II 2 D Ex tD A21 IP68 T80 C
89115889