Page 1
synergy ™ Quick Start Guide HPat 440- Type le A kW at 400V UL.FLA A 480V SGY-101 SGY-103 SGY-105 SGY-107 18.5 SGY-109 SGY-111 SGY-113 SGY-115 SGY-117 Ie AC-53a:3.5-17:90-5...
Page 2
Redefining Motor Control As the original pioneers of soft start technology Fairford Electronics Ltd have been at the forefront of motor control innovation since the 1970’s. A major designer and manufacturer of soft start motor control solutions Fairford have manufactured and supplied over 1 million products into the market place and are recognised as the reference point for many control solution providers worldwide.
Page 3
Environment - installation Dimensions Fitting 95mm (3¾”) 95mm (3¾”) 25mm (1”) 25mm (1”) 25mm (1”) 60mm 60mm 176mm (6 ⁄ ”) 176mm (6 ⁄ ”) (2 ⁄ ”) (2 ⁄ ”) Weight = 3.5kg SECTION A-A Enclosure Ventilation When fitting synergy into a cabinet, ventilation must be provided if the heat output of the unit is greater than the cabinet will dissipate.
Page 5
Wiring connection In Line In Delta K1 - Main contactor and protection switch gear K1 - Main contactor or (provided by the customer) circuit breaker isolation and protection switch gear For this configuration (provided by the customer) applying the equation. synergy™...
Page 6
Programmes Please note; Only appears if application with a trip class higher than 10 is selected...
Page 7
Rating table 220- 440- Type 230v 400v 200v 208v SGY-101 SGY-103 SGY-105 SGY-107 18.5 SGY-109 SGY-111 SGY-113 18.5 SGY-115 SGY-117 • Rated operational powers in kW according to IEC 60072-1(primary series) corresponding to IEC current rating optimised for 400V • Rated operational powers in hp according to UL508 corresponding to FLA current rating(optimised for 440-480v) •...
Page 8
Technical information Motor overload 'cold' trip curves (20°C ambient) 1000
100
10
1
1
1.5
2
2.5
3
3.5
4
4.5
Multiple of Motor FLA Class10
Class20
Class30
...
Page 9
Technical information/Standards Rated operational voltages 230Vac to 480Vac Rated operational current See model ratings table below Rating index : AC-53a:3.5-17: 90-5 Rated frequency/frequencies 45 to 65Hz Rated duty Uninterrupted Form designation Form 1 Internally bypassed Rated insulation voltage 480V Main circuit Rated impulse withstand voltage Control supply circuit...
Page 10
Standards -20°c (-4°f) to 50°c (122°f) above 50°c de-rate by 2% per degree to a maximum of 60°c (140°f). Maximum altitude above sea level 1000m (3281ft) above 1000m de rate by 1% per 100m (328ft) to a maximum altitude of 2000m (6562ft). Please note for higher temperatures and altitudes contact your supplier.
Page 12
Livsfara genom elektrisk ström! Toate lucrările descrise trebuie efectuate numai de personal de specialitate calificat şi Endast utbildade elektriker och personer som undervisats i elektroteknik får utföra de arbeten de persoane cu cunoştiinţe profunde în electrotehnică. som beskrivs nedan. info@fairford.com www.fairford.com...