Download Print this page

Dunkirk ESB0365 Installation Manual And Operating Instructions page 12

Empire steam ii oil-fired cast iron boiler

Advertisement

D. Set room thermostatto call for heat, or jump
thermostatcontactson the boilercontrol.
E. Openall oil linevalves.
F. Turn serviceswitchon. Burnershouldstart.
G. On one pipe fuel systemsonly, bleed pumpas
soonas burnerstarts.Allowoil to rununtilalltraces
of air in the suctionlinedisappear.
H. Turn "OFF"burner and install pressuregauge
port on pump.
I. Startburneragainandcheckoil pressurefor 140
Ibs.Adjustif necessary.
A 1/4" diameter
slot is provided
in the inspection
cover
plate to take draft readings
in the combustion
chamber.
(Figure 12) A 1/4" diameter
hole will be required in the flue pipe between the boiler and barometric
damper
(if used) to take draft, CO2, smoke
and temperature
readings.
Adjust air shutter
on oil burner to
obtain a "trace" of smoke.
Measure
CO 2at this point. Increase
air adjustment
to lower CO 2 approximately
one percent.
Check to insure minimum
negative
.02 w.c., (water column),
"overfire"
draft and zero smoke.
If -.02 w.c. "overfire"
draft can not be maintained,
changes
and/or
modifications
may be required
in the
venting or the chimney.
The following
tables are provided
as a guideline
for initial start-up.
Final adjustments
MUST be made using
combustion
instruments
as previously
mentioned.
RIELLO
SETTINGS
..... _le
_
i:
N
Ai
Da_
i
; P_
ESB3100
F-5
3.6
150 PSi
1
.85 80W
ESB4125
F-5
4
150 PSI
3
1.10 60W
ESB4150
F-5
6
150 PSI
4
1.25 60W
ESB5200
F-10
5
150 PSI
0
1.75 80B
CARLI N SETTINGS
ESB3100
EZ-1
0.85
150 PSI
.85-1.00
.85 70B
ESB4125
EZ-1
1.00-1.10
150 PSI
1.10-1.25
1.10 70B
ESB4150
EZ-1
1.25-1.35
150 PSI
1.10-1.25
1.25 70B
ESB5200
EZ-2
1.75
150 PSI
1.65-1.75
1.75 70B
BECKETT SETTINGS
ESB3100
AFG
1
5
140 PSi
3-3/8U
F3
.85 80B
ESB4125
AFG
1
8
140 PSI
2-3/4"
F4
1.10 80B
ESB4150
AFG
2
6
140 PSI
2-3/4"
F6
1.25 80B
ESB5200
AFG
5
5
140 PSI
3U
F12
1.75 70B H
ESB6225
CF375
4
6
140 PSI
L1
N/A
2.00 45B
ESB7275
CF375
4
6
140 PSI
L1
N/A
2.25 45B
NOTES:
(1) Model ESB6225
needs a head setting of 1 and ESB7275 needs a head setting
of 2.
(2) Nozzle sizes with an H designation
are Hago brand, all others are Delevan.
(3) Information
in above table uses Beckett model AFG burner for model numbers
ESB365-5200
and Beckett
model CF375 for model numbers
6225 and 7275.
IMPORTANT:
Check
safety control
circuit
after burner
adjustments
have been
made for satisfactory
performance,
i)

Advertisement

loading

This manual is also suitable for:

Esb3100Esb4125Esb4150Esb5175Esb5200Esb7275 ... Show all