Installation - Re-Verber-Ray MP-25-80N Insert Manual

Mp series modulating plus tube heater
Table of Contents

Advertisement

2.0
Installation • Gas Requirements • Electrical Requirements
2.0

Installation

Improper installation, adjustment, alteration, service or maintenance can cause property
damage, serious injury or death. Read and understand the installation, operating and
maintenance instructions thoroughly before installing or servicing this equipment. Only
trained, qualified gas installation and service personnel may install or service this equipment.
Not for residential use! Do not use this heater in the home, sleeping quarters, attached
garages, etc. Installation of a commercial tube heater system in residential indoor
spaces may result in property damage, serious injury or death.
Instructions for the following are detailed in the Tube Heater General Manual:
• Design considerations
• Hanger suspension and placement
• Tube layout and assembly
• Burner control box suspension
• Reflectors (and accessories)
• Venting and combustion air intake
• Gas requirements
• Baffle assembly
Note: Electronic versions of all manuals are available at www.detroitradiant.com, or upon request.
Gas Requirements
Manifold pressure of the heater is pre-set at the factory. No adjustment should be necessary.
During the verification process, a tolerance of ±10% of the full scale is acceptable due to varying
atmospheric conditions.
Type of Gas
@ Maximum Rate
Natural
4.10 Inches. W.C.
Propane
11.0 Inches. W.C.
IMPORTANT: Consult the Tube Heater General Manual for gas connection requirements.
Electrical Requirements
• 120 Volt - 60 Hz GRD, 3-wire.
• Low voltage thermostat connection.
• Starting current 4.8 amps.
• Running current 1.1 amps.
Shielded thermostat wire of 18 AWG is recommended for connection to the heater from the thermostatic
controller. The MP Series heater is pre-set by the factory for use with the Premium User Interface (TP-PUI).
WARNING
!
Manifold Pressure
@ Minimum Rate
1.65 Inches W.C.
4.80 Inches W.C.
NOTICE
Minimum
6.00 Inches W.C.
12.00 Inches W.C.
6
MP
Series
Inlet Pressure
Maximum
14.00 Inches W.C.
14.00 Inches W.C.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents