6. Operation setting

6.1. Automatic change over mode
When a system includes a Domestic Hot Water (DHW) tank and a space heating requirement Automatic change over mode should be selected.
Selection is made with Dip SW1-8.
If the system does NOT include a DHW tank Dip SW 1-3 is ON and Automatic change over mode is invalid.
SW 1-8
Operation
OFF
With Automatic change over mode (the system has a DHW tank).
Without Automatic change over mode (the system does NOT have a DHW tank).
ON
OR The end user would like to control the switch over between DHW and space heating.
Operations on each mode with Automatic change over mode.
Mode
System operation
Heating
Heating and DHW (Automatic change over mode)
Heating ECO
Heating with Weather compensation and DHW (Automatic change over mode)
Hot Water
Domestic Hot Water only
Anti-freeze
Prevents pipe work freezing during periods of inactivity
Operations on each mode without Automatic change over mode.
Mode
System operation
Heating
Heating only
Heating ECO
Heating only with Weather compensation
Hot Water
Domestic Hot Water only
Anti-freeze
Prevents pipe work freezing during periods of inactivity
When automatic change over mode is selected DHW always has priority over space heating.
System examples
Example 1:
Only our Remote controller (PAR-W21MAA) is used for system control.
NO local system controller exists.
Target temperature for each mode and Heating or Heating ECO mode are set
with PAR-W21MAA. Automatic change over mode is selected (SW 1-8 must
be switched to OFF). The system will automatically change from Heating or
Heating ECO to DHW mode and back dependent on the DHW tank tem-
perature (TH5).
Example 2:
A local timer and our Remote controller (PAR-W21MAA) are used
for system control.
Target temperature for each mode and Heating or Heating ECO mode are set
with PAR-W21MAA.
A local timer is used rather than automatic change over mode (SW1-8 must
be switched to ON). The system runs in Heating or Heating ECO until a signal
is received from the local timer (the signal received from local timer must
be longer than 5 secs). The system then switches to DHW mode.
Once DHW mode is satisfied the system automatically reverts to Heating or
Heating ECO.
14
RG79D525H01_EN.indd 14
RG79D525H01_EN.indd 14
SW 1-1 OFF / SW 1-2 OFF / SW 1-8 OFF
Flow
switch
IN1
IN2
IN3
IN4
IN5
IN6
Emergency
Legionella
Comp
Cooling
Heating
Heating
prevention
OFF
ECO
TH1
TH1
FTC2
TH2
TH2
TH5
TH5
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7
Water
Booster
3-port
circulation
heater 2
valve
pump Booster
Immersion
Defrost
heater 1
heater
SW 1-1 OFF / SW 1-2 OFF / SW 1-8 ON
Local timer
External input
Flow
switch
IN1
IN2
IN3
IN4
IN5
IN6
Emergency
Legionella
Comp
Cooling
Heating
Heating
prevention
OFF
ECO
TH1
TH1
FTC2
TH2
TH2
TH5
TH5
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7
Water
Booster
3-port
circulation
heater 2
valve
pump Booster
Immersion
Defrost
heater 1
heater
IN7
IN8
Hot
Anti
Water
freeze
PAR-W21MAA
Error
IN7
IN8
Hot
Anti
Water
freeze
Error
PAR-W21MAA
2009/04/10 9:24:41
2009/04/10 9:24:41