Digital Input (Di Function) [Option] - Fuji Electric PXR4 Instruction Manual

Micro-controller x
Hide thumbs Also See for PXR4:
Table of Contents

Advertisement

6-7 Digital input (DI function) [option]

1) Function
·
With Digital input, the follwing functions are available.
q SV switching
w Control mode; RUN/STANDBY selection
e Ramp/soak RUN/RESET selection
r Auto-tuning start/stop
t Alarm latch cancel
y Timer start/reset
2) To use DI function;
·
Select the function with the parameter "di-1" or "di-2 " refering to the Table shown below.
3rd block parameter
PV
SV
3) Table of DI function
DI
Function
function
code
1
Set value (SV) switcing
2
Control mode, RUN/STANDBY At standby mode, control is not provided and SV flickers.
3
Auto-tuning (standard)
start
4
Auto-tuning (low PV)
start
5
All alarm latch cancel
6
Alarm 1 latch cancel
7
Alarm 2 latch cancel
8
Alarm 3 latch cancel
9
ALM1 timer
10
ALM2 timer
11
ALM3 timer
12
Ramp/soak RUN/RESET RUN/RESET of ramp/soak can be performed at the time
or
DI function code
(0 to 12)
Switching between local SV and "
Start/Stop can be switched at the time of DI raising up or
dropping down.
When this function is not used, DI is not effective.
ON/OFF delay timer operation is available. The remaining
time of the timer can be checked with timer-1 and -2
display parameters (first block).
of DI raising up or dropping down.
– 26 –
Description
" "
" "
"

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents