The sensor is a solar powered device that absorbs energy through a solar panel;
storing it for use during low light periods. Before assigning the sensor to a
receiver/controller, the RVS must be exposed to a good light source for at least
2 minutes.
1. Remove the cover by inserting a small screwdriver under the white
enclosures lip. Gently twist the screw driver and pull the cover away from
the base.
2. Activate LEARN or LINK mode at the receiver, if necessary refer to the
manufacturers documentation.
3. Press the sensors LINK button.
4. Deactivate LEARN mode at the receiver.
Installing or Replacing the Battery
The battery is not required for normal
operation when the RVS receives
adequate natural or artificial light,
minimum 6 foot candles or 65 lux.
The RCS model comes with a battery
(requires installation).
1. Remove the cover by inserting a small
screwdriver under the white enclosures lip. Gently twist the screw driver
and pull the cover away from the base.
2. To remove an old battery, use a small screwdriver as a lever and insert
under the battery. Gently twist the screwdriver so the battery pops out.
3. Install or replace the battery with a new CR1632 coin cell battery insuring
the positive side (+) will be facing up.
4. Place the battery in the holder and press in place with your thumb.
Test Operating Modes
Test modes require a battery to be installed. For RVS units, insert a CR1632
battery to run tests.
NOTE: An alternative to installing a battery is to use a bright light (hand-held
LED light, or Smart Phone) and shine this on the sensor while in test mode.
Depending on the light used, this may provide sufficient energy to run the test
selected. Do not use this method for Light Level Test, Walk Test Mode or Range
Confirmation .
Remove the cover for access to the test button.
The following 4 tests can be selected when in test mode operation.
Light Level Test:
1. To enter Light Level Test mode, press and hold the test button for 6 seconds.
The green LED will begin to blink (LEDs are located under the lens).
2. Press the test button again for 6 seconds to select Light Level Test. The
green LED will blink in accordance to the light level it is detecting. This will
Battery Holder
Link Button
5