Resonate wireless vacancy/occupancy sensor

Advertisement

change (2 second lag time) if you move the sensor to areas with different
light levels. See blink indicator table on the next page.
The green LED will blink according to the energy produced by the solar cell
Blinks
0
1
2
3
4
5
The test will repeat every 2 seconds and run for a duration of 100 seconds. You
may quit the test at any time by pressing the Test button for 10 seconds.
Range Confirmation Test: provides visual feedback of the sensors signal
strength by a linked receiver with range confirmation capability (only "F series"
controllers have range confirmation ability). Have only one receiver linked to the
sensor for proper operation of the test and disable repeaters in range for proper
test operation).
The Range Confirmation test requires a battery to be installed.
1. To enter Range Confirmation Test mode, press and hold the test button for
6 seconds. The green LED will begin to blink.
2. A quick press and release of the button at this point will allow you to select
between test modes. Pressing and releasing the test button scrolls through
the LED indicators. When the amber LED is blinking, go to step 3.
3. Press and hold the test button again for 6 seconds to select Range
Confirmation Test.
4. All three LED's will blink (for 1 second) in this test mode when the sensor
transmits or receives a Range Confirmation Telegram followed by the
sensor displaying the linked signal strength status for 2.5 seconds.
Green - Blinking 2.5 sec
Amber - Blinking 2.5 sec
Red - Blinking 2.5 sec
No LED
The test will repeat every 4 seconds and run for a duration of 50 seconds. You
may quit the test at any time by pressing the test button for 10 seconds.
Walk Test Mode: In walk test mode, the red LED will blink on every motion event.
This allows an installer to verify the sensor can monitor and detect motion in an
area as required.
1. To enter Walk Test mode, press and hold the Test button for 6 seconds. The
green LED will begin to blink.
6
LIGHT LEVEL TEST TABLE
Lux
Foot Candles
0
0
50-100
4.5 to 9
100-200
9 to 18
200-400
18 to 36
400-800
36 to 72
800+
72+
RANGE CONFIRMATION TEST TABLE
LED
Charge Level
below operating level
min. operating level
operational
operational
operational
operational
Signal Strength
-41 to -70 dBm
-70 to -80 dBm
-80 to -95 dBm
No linked receivers detected