Installation
4.3.2
18

Connecting the cables

► If a protective conductor is provided or required for the pump,
connect the protective conductor to the terminal clamps of the
controller. When connecting the protective conductor, observe
then following points:
Make sure that the grounding contact is also connected to
the controller's mains supply side.
Each terminal may only be connected to a single
connecting wire (max 2.5 mm²).
The terminals are suitable for connection without sleeves;
stranded wires are to be twisted (1 twist per 20 mm).
► Only use the original temperature sensors (Pt1000) that are
approved for use with the controller.
► Observe the following points:
The polarity of the sensor contacts is not important.
Do not lay sensor cables close to 230 volt or 400 volt
cables (minimum separation 100 mm).
If inductive effects are expected, e.g. from heavy current
cables, overhead train cables, transformer substations,
radio and television devices, amateur radio stations,
microwave devices etc., then the sensor cables must be
adequately shielded.
Sensor cables may be extended to a maximum length of
100 m.
► When using extension cables, select the following cable cross
sections:
0.75 mm² up to 50 m long
1.5 mm² up to 100 m long
► Connect the cables in accordance with the terminal plan.
ASC02-01WM
EN2B-0365GE51 R0710