ACL CSC400 Installation And Operation Manual page 29

Combustion safety controller
Table of Contents

Advertisement

2.1.14
2.1.15
2.1.16
2.1.17
2.1.18
2.1.19
2.1.20
2.1.21
2.1.22
2.1.23
2.1.24
2.1.25
2.1.26
2.1.27
2.1.28
2.1.29
2.1.30
2.2
Line Display
Config
2.3
Temp Setpoints
2.4
Show Last IGN
SD
2.5
TMain 1 On
Time View
2.6
TMain 2 On
Time View
Dual TC1&2 SD No
4-20 Out Settings
4-20 In 1 Settings
4-20 In 2 Settings
Purge Cycle
10s
IGN Int-Purge 0s
AUX1 Relay Settings
AUX2 Relay Settings
PWR Save Disabled
PWR Fail
Latched
High Temp Latched
Hi Tmp TC3 Latched
High Gas
Latched
Low Gas
Latched
Level
Latched
Aux 1
Latched
Aux 2
Latched
Line 1: TC1 temp w setpoint
Line 2: TC2 temp w setpoint
Line 3: FI mode VLVs 1
TC1 IGN1 Set
200°C
TC1 IGN2 Set
300°C
TC2
Set
600°C
TC3
Set
400°C
Low Temp Set
200°C
Deadband TC1 IGN1 1
Deadband TC1 IGN2 1
Deadband TC2
1
Deadband TC3
1
Years
Hours
Months
Minutes
Days
Reset TMain 1 Timers
Years
Hours
Months
Minutes
Both Ignitors must be enabled for this option to
have an effect on the Alarm/Status contacts
Option
Dual TC1&2 10°C Difference Shutdown Y/N
Yes: Shutdown if TC1 & 2 are different by greater
than 10°C (18°F)
No: No link between TC1 & TC2
Menu
4-20mA Output Settings Menu
Menu
4-20mA Input 1 Settings Menu (Level)
Menu
4-20mA Input 2 Settings Menu (Press.)
Option
Purge Cycle Time (0s - 300s) (before first ignition
trial)
Option
Extra Inter-Purge Time (0s - 240s) between
Ignitor relight trials.
Menu
AUX1 Relay Settings Menu
Menu
AUX2 Relay Settings Menu
Option
Power Save Enable/Disable
Option
Power Fail Shutdown Latched/Unlatched
Option
High Temp Shutdown Latched/Unlatched
Option
TC3 High Temp SD Latched/Unlatched
Option
High Gas Shutdown Latched/Unlatched
Option
Low Gas Shutdown Latched/Unlatched
Option
Level Shutdown Latched/Unlatched
Option
Auxiliary 1 Shutdown Latched/Unlatched
Option
Auxiliary 2 Shutdown Latched/Unlatched
Menu
Line Display Configuration - Select items to
display on the three top lines on the display
Option
Select information to display for Line 1
Option
Select information to display for Line 2
Option
Select information to display for Line 3
Menu
Option
Change TC1 Ignitor 1 Setpoint temperature
Change TC1 Ignitor 2 Setpoint temperature
Option
Change TC2 Setpoint temperature
Option
Change TC3 Setpoint temperature
Option
Change Low Temp SD/ALM Setpoint temperature
Option
Set Deadband for TC1 IGN1: 1-5°C or 2-10°F
Option
Set Deadband for TC1 IGN2: 1-5°C or 2-10°F
Option
Set Deadband for TC2: 1-5°C or 2-10°F
Option
Set Deadband for TC3: 1-5°C or 2-10°F
Information
Show the last shutdown(s) for IGN 1 / 2 and the
time and date that they occurred
Menu
Display time that the TMain 1 solenoid has been
on since the last TMain timer reset
Information
Information
Information
Option
Reset TMain 1 solenoid timers
Menu
Display time that the TMain 2 solenoid has been
on since the last TMain timer reset
Information
Information
29