4.2.4. Structure and function
Summary of racking data
table 2. Summary Racking data
Distance from Disconnected
Manual opening
Electrical Operation
Control Power Available
Shutter
Primary Contacts Engaged
Requirements to rack breaker from position
Notes
Notes A: Closed door is mandatory between all positions
Secondary
disconnects (B)
fig. 4
12
0 mm / 0 revolutions / 0 inches
Yes, while power cord is connect
Yes, while power cord is connect
Breaker Open / Power cord connect
Shutters
Racking screw collar
diSConneCt
Yes
CLOSED
No
A
Wheel rails
Compartment slots
ConneCt
200 mm / 20 revolutions / 7.89 inches
Not recommended unless necessary
Yes, while power cord is connect
Yes
OPEN
Yes
Breaker Open / Power cord connect
A
Need help?
Do you have a question about the VM1 and is the answer not in the manual?
Questions and answers