Additional Requirements For Stainless Steel Vent Pipe Material - Viessmann Vitodens 100-W WB1A-24 Installation Instructions Manual

Venting system, wb1a/wb2 series, with preinstalled vent pipe adaptor
Table of Contents

Advertisement

Single Wall Venting (Room Air Dependent)
General Installation Information

Additional requirements for stainless steel vent pipe material

Use an AL29-4C® special stainless
steel venting system (UL/ULC listed for
category IV) for horizontal or vertical
venting of the Vitodens boilers.
See tables 42. and 43. and contact
one of the suppliers (see listing on
right) to order.
Prior to installation, check that the
correct single-wall vent parts were
ordered and supplied.
See tables 42. and 43. for special
stainless steel single-wall vent pipe
starter adaptor, coaxial increasers and
bird screen models required for your
installation. In case of discrepancies,
contact original parts supplier.
Exhaust vent pipe connection to boiler
The vent connection to the Vitodens
boiler must be made with a coaxial
increaser (Vitodens 100-W only) and
starter stainless steel adaptors
(supplied by others, see tables 42. and
43.). The starter adaptors are intended
for a slip fit and slide into the boiler
adaptor with a gentle twisting motion.
Note:
For stainless steel exhaust vent
system, the minimum pipe diameter is
3" / 76mm.
64
(continued)
Note:
The Vitodens boiler has passed the
zero inches vent clearance to
combustibles testing requirements
dictated by the Harmonized Standard
ANSI Z21.13. CSA 4.9.2000 and
therefore is listed for zero clearance to
combustibles when vented with a
single wall special venting system. The
zero inches vent clearance to
combustibles for the Vitodens boiler
supercedes the clearance to
combustibles listing that appears on
the special venting system label.
Flexmaster Canada Ltd.
452 Attwell Drive
Etobicoke, ON
M9W 5C3
Tel. (416) 679-0045
Z-FLEX (US) INC.
20 Commerce Park North
Bedford, NH
03110-691
Tel. (800) 654-5600
Flex-L International Inc.
6385 Kennedy Road
Mississauga, ON
L5T 2W4
Tel. (800) 561-1980
Flex-L International Inc.
P.O. Box 29140
Columbus, OH
43229-0140
Tel. (800) 561-1980
Heat-Fab, Inc.
130 Industrial Blvd.
Turners Falls, MA
01376
Tel. (800) 772-0739
ProTech Systems, Inc.
400 South Pearl Street
Albany, NY
12202
Tel. (800) 766-3473
Security Chimneys International Ltd.
2125 Rue Monterey
Laval, QC
H7L 3T6
Tel. (800) 363-0821
IMPORTANT
For exhaust vent pipe material:
Do not use any other vent material.
Do not use galvanized pipe, plastic pipe
and/or chimney liners of any kind.
WARNING
The use of vent material other than
AL29-4C stainless steel, positive
pressure vent pipe and fittings can
cause property damage, severe
personal injury and/or loss of life.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents