Side Wall Vent Installation
Side Wall Venting Layouts
Layout with basic coaxial vent kit and accessory componentry
Fig. 4
Side wall venting layout, using basic vent kit components and accessory parts
for vent system 60/100, 80/ 125 and 100/150
14
(continued)
Straight pipe
*1
3.3 ft./1 m long
or
1.6 ft./0.5 m long
Vent inspection tee/
Elbow, 87° (1 per carton)
Sliding coupling
Elbow, 45° (2 per carton)
Vent termination
(incl. wall flashings)
Important!
Total length of vent termination is
31"/787 mm. If required, the vent
termination may be shortened by max.
12"/305 mm (min. vent
termination length is 19"/483 mm).
Protective screen
Warning!
Protective screen must be installed.
Mounting clip, white (use at least 2)
5
Brass adaptor (M8 x
/
" - 18) and
16
3
Set of screws (#8 x
/
")
8
*1
Other lengths may be used provided that the
maximum equivalent vent length is not exceeded.