Securing The Outdoor Unit - Lennox MPA012S4S-1P Installation Instructions Manual

Mla series; mpa series; mpb series; m22a series; m33a series; m33b series
Hide thumbs Also See for MPA012S4S-1P:
Table of Contents

Advertisement

rubber plugs to cover any unused drain holes (see "Figure
23. Condensate Drain" on page 16).
Drain
Connector
Figure 23. Condensate Drain

Securing the Outdoor Unit

Slab or Roof Mounting
Install the unit a minimum of 4 inches (102 mm) above the
roof or ground surface to avoid ice build-up around the
unit. Place the unit above a load bearing wall or area of
the roof that can adequately support the unit. Consult local
codes for rooftop applications.
CAUTION
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil. This will cause
the rubber to swell when it comes into contact with oil.
The rubber will then bubble and could cause leaks.
Protect the roof surface to avoid exposure to refrigerant
and oil during service and installation. Failure to follow
this notice could result in damage to roof surface.
Securing Outdoor Unit to Slab, Frame, or Rails
If the outdoor unit is installed on a field-provided slab or
frame, use lag bolts or equivalent to secure the outdoor
unit to the slab or frame.
Four Field-provided Anchor Bolts
Figure 24. Securing Outdoor Unit to Slab
Condensate Drain
(location varies per model)
Chassis
Figure 25. Securing Outdoor Unit to Rails
Securing Outdoor Unit to Hanging Brackets
If the outdoor unit is installed on field-provided wall
mounting brackets, use lag bolts or equivalent to secure
the outdoor unit to the bracket. Minimum rear clearance
can be reduced to 6 inches (152 mm) when mounted
on brackets and with no obstructions on the other three
sides. Allow for condensate disposal when placing units
above one another.
Air Outlet
Figure 26. Securing Outdoor Unit to Brackets
16
Four Field-Provided
Anchor Bolts
6 in
152 mm
Air Inlet