Buried Refrigerant Pipe Protection; Outdoor Unit Condensate Piping; Securing The Outdoor Unit - Lennox 3PC036 Installation Instruction

Table of Contents

Advertisement

Outdoor unit can be installed in a alcove or under
a roof overhang as illustrated in "Figure 19. Unit In-
stalled in Alcove".
Prevailing Winter Winds from Air Inlet Side
Prevailing Winter Winds From Air Discharge Side
Figure 17. Wind Barrier
24 in
610 mm
12 in
305 mm
NOTE - Minimum clearances shown.
Figure 18. Dog House-Style Shelter
12 in
305 mm
NOTE - Minimum clearances shown.
Figure 19. Unit Installed in Alcove

Buried Refrigerant Pipe Protection

All refrigerant lines must be insulated regardless of if
it is buried.
Wind Barrier
Inlet Air
12" (305mm)
Min. Distance
79" (2007mm)
Min. Distance
Discharge Air
Wind Barrier
24 in
610 mm
12 in
305 mm
24 in
610 mm
12 in
305 mm
24 in
610 mm
In addition to insulating each line of piping, buried lines
must rest inside a sealed, watertight conduit.
The conduit must be designed so it cannot collect and
retain water.

Outdoor Unit Condensate Piping

Condensate formed during the heating and defrost
processes must be drained from heat pump units. Drain
holes are provided in the base of the units to ensure proper
drainage. Heat pumps must be raised when installed on a
concrete pad or the ground to allow drainage to occur. If
the heat pump unit is installed on wall mounting bracket,
insert the provided drain connector into one of the 1
inch (25 mm) drain holes and attached a field-provided
insulated drain hose to the connector. Use field-provided
rubber plugs to cover any unused drain holes as illustrated
in "Figure 20. Condensate Drain".
Drain
Connector
Figure 20. Condensate Drain

Securing the Outdoor Unit

Slab or Roof Mounting
Install the unit a minimum of 4 inches (102 mm) above the
roof or ground surface to avoid ice build-up around the
unit. Place the unit above a load bearing wall or area of
the roof that can adequately support the unit. Consult local
codes for rooftop applications.
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil. This will cause
the rubber to swell when it comes into contact with oil.
The rubber will then bubble and could cause leaks.
Protect the roof surface to avoid exposure to refrigerant
and oil during service and installation. Failure to follow
this notice could result in damage to roof surface.
Securing Outdoor Unit to Slab, Frame, or Rails
If the outdoor unit is installed on a field-provided slab or
frame, use lag bolts or equivalent to secure the outdoor
unit to the slab or frame.
12
Condensate Drain
(location varies per model)
Chassis
CAUTION

Advertisement

Table of Contents
loading

This manual is also suitable for:

3wmc036

Table of Contents