Electrical Data - LG MULTI F Engineering Manual

Multi f; multi f max with lg red heat pump outdoor unit
Hide thumbs Also See for MULTI F:
Table of Contents

Advertisement

MULTI F WITH LGRED
General Data / Electrical Data
General Data, continued.
Table 8:
System
Combined With
Non-Ducted Indoor Units
Ducted Indoor Units
LMU180HHV
Mixed Non-Ducted and
Ducted Indoor Units
Table 9:
System
Combined With
Non-Ducted Indoor Units
Ducted Indoor Units
LMU240HHV
Mixed Non-Ducted and
Ducted Indoor Units
Table 10:
System
Combined With
Non-Ducted Indoor Units
Ducted Indoor Units
LMU300HHV
Mixed Non-Ducted and
Ducted Indoor Units
Rated capacity is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor
1
units. All capacities are net with a combination ratio between 95 – 105%.
Rated cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions
of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Rated heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB) and outdoor ambient conditions
of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
values.
At least two indoor units must be connected. For allocated capacity information, see the combination tables in the "Multi F / Multi F MAX with
LGRED Combination Data Manual" on www.lg-dfs.com. For performance data, see "Multi F / Multi F MAX with LGRED Performance Data Manual"
on www.lg-dfs.com.

Electrical Data

Table 11: Electrical Data.
Nominal
Unit Model No. Hertz Voltage
Tons
1.5
LMU180HHV
2
LMU240HHV
60
2.5
LMU300HHV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded
down to the nearest standard fuse size.
16 | MULTI F WITH LGRED
1,2
Rated Cooling
EER
Capacity (Btu/h)
(95°F)
18,000
13.5
16,500
12.0
17,250
12.75
1,2
Rated Cooling
EER
Capacity (Btu/h)
(95°F)
24,000
13.5
20,000
11.5
22,000
12.5
1,2
Rated Cooling
EER
Capacity (Btu/h)
(95°F)
28,400
12.5
24,600
10.5
26,500
11.5
Voltage
Range
MCA
(Min. to Max.)
18.6
208 - 230
187 - 253
19
19.4
RFA = Recommended Fuse Amps.
RLA = Rated Load Amps.
FLA = Full Load Amps.
©
Rated Heating
SEER
Capacity (Btu/h)
21.0
22,000
17.5
22,000
19.25
22,000
Rated Heating
SEER
Capacity (Btu/h)
21.0
26,000
17.0
24,000
19.0
25,000
Rated Heating
SEER
Capacity (Btu/h)
(47°F)
20.0
28,600
17.5
27,000
18.75
27,800
Compressor
Compressor
MOP
RFA
Quantity
Motor RLA
30
25
1
30
25
1
30
25
1
Indoor Fan Motor (FLA) is based on the max. combination of IDUs.
The maximum combination for each outdoor unit is:
- 18,000 ODU (LMU180HHV): 12,000 IDU x 2
- 24,000 ODU (LMU240HHV): 12,000 IDU x 2 + 9,000 IDU x 1
- 30,000 ODU (LMU300HHV): 12,000 IDU x 3
F
MULTI
WITH
COP
Low Heating
HSPF
(47°F)
Capacity (Btu/h)
2.9
10.0
14,700
2.6
9.0
14,700
2.75
9.5
14,700
COP
Low Heating
HSPF
(47°F)
Capacity (Btu/h)
3.6
10.7
17,400
2.9
9.0
15,200
3.25
9.85
16,300
COP
Low Heating
HSPF
Capacity (Btu/h)
3.6
11.0
18,900
3.1
9.5
17,700
3.35
10.25
18,300
Outdoor Fan Motor
kW
FLA
13
0.12
0.73
13
0.12
0.73
13
0.12
0.73
COP
(17°F)
2.5
2.3
2.4
COP
(17°F)
2.8
2.3
2.5
COP
(17°F)
2.8
2.5
2.7
Indoor
Fan Motor
FLA
1.6
2.0
2.4