LG MULTI F Engineering Manual page 30

Multi f; multi f max with lg red heat pump outdoor unit
Hide thumbs Also See for MULTI F:
Table of Contents

Advertisement

MULTI F MAX WITH LGRED
General Data / Electrical Data
General Data
Table 18:
System
Combined With
Non-Ducted
Indoor Units
LMU360HHV
Ducted Indoor Units
Mixed Non-Ducted and
Ducted Indoor Units
Table 19:
System
Combined With
Non-Ducted
Indoor Units
LMU420HHV
Ducted Indoor Units
Mixed Non-Ducted and
Ducted Indoor Units
Rated capacity is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor
1
units. All capacities are net with a combination ratio between 95 – 105%.
Rated cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions
of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Rated heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB) and outdoor ambient conditions
of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
values.
At least two indoor units must be connected. For allocated capacity information, see the combination tables in the "Multi F / Multi F MAX with
LGRED Combination Data Manual" on www.lg-dfs.com. For performance data, see "Multi F / Multi F MAX with LGRED Performance Data Manual"
on www.lg-dfs.com.
Electrical Data
Table 20: Electrical Data.
Nominal
Unit Model
Hertz Voltage
Tons
No.
3.0
LMU360HHV
60 208 - 230
3.5
LMU420HHV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
30 | MULTI F MAX WITH LGRED
1,2
Rated Cooling
EER
Capacity (Btu/h)
(95°F)
36,000
15.0
34,000
13.5
35,000
14.25
1,2
Rated Cooling
EER
SEER
Capacity (Btu/h)
(95°F)
42,000
14.0
42,000
13.0
42,000
13.5
Voltage
Compressor
Range
MCA MOP
(Min. to Max.)
30.2
45
187 - 253
30.2
45
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded
down to the nearest standard fuse size.
©
Rated Heating
COP
SEER
Capacity (Btu/h)
(47°F)
21.0
41,000
4.1
17.5
40,000
3.3
19.25
40,500
3.7
Rated Heating
COP
Capacity (Btu/h)
(47°F)
20.5
45,000
4.0
19.0
45,000
3.6
19.75
45,000
3.8
Compressor
Outdoor Unit Fan Motor(s)
Quantity
Motor RLA
kW x Quantity
1
20.4
0.12 x 2
1
20.4
0.12 x 2
RLA = Rated Load Amps.
FLA = Full Load Amps.
Indoor Fan Motor (FLA) is based on the max. combination of IDUs.
F
MULTI
MAX
WITH
Low Heating
HSPF
Capacity (Btu/h)
11.5
28,000
10.5
27,000
11.0
27,500
Low Heating
HSPF
Capacity (Btu/h)
11.0
29,000
10.5
29,000
10.75
29,000
Indoor Unit Fan
Motor
FLA x Quantity
FLA
0.73 x 2
3.2
0.73 x 2
3.2
COP
(17°F)
2.9
2.5
2.7
COP
(17°F)
2.8
2.7
2.75

Hide quick links: