[ VIII Test Run Mode ]
Model name of BC controller
Indoor temperature
Heat source water temperature
Heat source water flow rate
Indoor
unit
Operating
conditions
Pipe
length
Fan speed
Refrigerant charge
Current
Heat source
Voltage
unit
Compressor frequency
Indoor unit
BC controller (1/2/3)
LEV opening
LEV6
LEV7
High pressure (after O/S)/
Low pressure (before accumulator)
Pressure
switch
BC controller on the liquid side
(PS1)/Intermediate part (PS3)
Heat
source
unit
Sectional
temperatures
Indoor
unit
HWE15060
Item
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
Discharge (TH4)
Heat exchanger outlet
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger outlet
PQRY-P300YLM-A
DB/WB
°C [ °F]
3
m
/h
5.76
G/h
[1522]
gpm
[25.4]
Unit
100/100/100/100/100/100
m [ft]
kg
[lbs-oz]
A
V
Hz
105
325/325/325/325/325/325
Pulse
41
3000
2.30/0.81
[334/117]
MPa
[psi]
65 [149]
35 [95]
8 [46]
8 [46]
°C [ °F]
19 [66]
42 [108]
- 248 -
2-unit combination
PQRY-P600YSLM-A
PQRY-P300YLM-A
CMB-P1013V-GA1
27°C/19°C [81 °F/66 °F]
30 [86]
5.76
[1522]
[25.4]
6
6
5 [16-3/8]
10 [32-3/4]
65 [213-1/4]
Hi
26.2 [58]
32.7
400
105
2000/2000/240
41
3000
2.30/0.81
[334/117]
2.20/2.20
[319/319]
65 [149]
35 [95]
8 [46]
8 [46]
19 [66]
42 [108]
19 [66]
6 [43]
GB