[1] System configuration

1. Table of compatible indoor units <PQHY>
The table below summarizes the types of indoor units that are compatible with different types of heat source units.
Heat
Composing units
source
units
P200
-
P250
-
P300
-
P350
-
P400
-
P450
-
P500
-
P550
-
P600
-
P400
P200
P450
P250
P500
P250
P550
P300
P600
P300
P700
P350
P750
P400
P800
P400
P850
P450
P900
P450
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given heat source unit exceeds the capacity of the heat source
unit, the indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a com-
bination of units so that the total capacity of the connected indoor units is at or below the capacity of the heat source unit
whenever possible.
HWE15060
Maximum total capacity
of connectable indoor
units
-
100 - 260
-
125 - 325
-
150 - 390
-
175 - 455
-
200 - 520
-
225 - 585
-
250 - 650
-
275 - 715
-
300 - 780
P200
200 - 520
P200
225 - 585
P250
250 - 650
P250
275 - 715
P300
300 - 780
P350
350 - 910
P350
375 - 975
P400
400 - 1040
P400
425 - 1105
P450
450 - 1170
Maximum number
of connectable in-
door units
1 - 17
P15 - P250 models
R410A series indoor units
1 - 21
1 - 26
1 - 30
1 - 34
1 - 39
1 - 43
2 - 47
2 - 50
1 - 34
1 - 39
1 - 43
2 - 47
2 - 50