[ VIII Test Run Mode ]
Indoor temperature
Heat source water temperature
Heat source water flow rate
Indoor
unit
Operating
conditions
Pipe
length
Fan speed
Refrigerant charge
Current
Heat source
Voltage
unit
Compressor frequency
Indoor unit
SC (LEV1)
LEV opening
LEV6
LEV7
Pressure
High pressure (after O/S)/
switch
Low pressure (before accumulator)
Heat
source
unit
Sectional
temperatures
Indoor
unit
HWE15060
Item
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
Discharge (TH4)
Heat exchanger outlet
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
PQHY-P300YLM-A
DB/WB
20°C/- [68°F/-]
°C [ °F]
20[68]
3
m
/h
5.76
[G/h]
[1522]
[gpm]
[25.4]
3
Unit
3
-
100/100/100
5 [16-3/8]
m [ft]
10 [32-3/4]
35 [115]
-
Hi
kg
13.6 [30]
[lbs-oz]
A
16.3
V
400
Hz
90
332/332/332
0
Pulse
122
3000
MPa
2.68/0.80
[psi]
[389/116]
81 [178]
5 [41]
4 [39]
4 [39]
°C [°F]
4 [39]
40 [104]
39 [102]
70 [158]
- 210 -
Heat source unit model
PQHY-P350YLM-A
20°C/- [68°F/-]
20[68]
7.20
[1902]
[31.7]
3
3
100/125/125
5 [16-3/8]
10 [32-3/4]
35 [115]
Hi
15.7 [35]
10.8
400
67
332/406/406
0
122
3000
2.68/0.80
[389/116]
77 [171]
5 [41]
4 [39]
4 [39]
4 [39]
40 [104]
36 [97]
70 [158]
GB