Application and properties
1.2

Applications

The CP 1242-7 GPRS V2 is intended for use in an industrial environment. The following
applications are supported by the CP:
Telecontrol applications
Sending messages by SMS
Communication with a control center
Communication between S7-1200 stations via a GSM network
TeleService via GPRS
A TeleService connection can be established between an engineering station with STEP 7
installed on it and a remote S7-1200 station via the GSM network.
You can use the TeleService connection for the following purposes:
Downloading project or program data from the STEP 7 project to the station
Querying diagnostics data on the station
With TeleService via GPRS, a switching station is required between the remote station and
engineering Station. This switching station can be a telecontrol server or, if there is no
telecontrol server in the configuration, a TeleService gateway. You will find detailed
information about both systems in the documentation , see References.
Other connections are not interrupted by a TeleService connection. You will find examples of
the structure in the section Configuration examples (Page 15).
10
The function is not dependent on the operating mode of the CP.
Via the CP 1242-7 GPRS V2, the CPU of a remote S7-1200 station can receive SMS
messages from the GSM network or send messages by SMS to a configured mobile
phone or an S7-1200.
The CP is configured in "Telecontrol" mode.
Remote S7-1200 stations communicate via the GSM network and the Internet with a
telecontrol server in the master station. The telecontrol server communicates with a
higher-level control system using the integrated OPC server function.
Depending on the GSM service being used and the mode of the CP, the communication
between remote stations with a CP 1242-7 GPRS V2 will be handled in different ways:
– Inter-station communication via a master station ("Telecontrol" mode)
In this configuration, connections between S7-1200 stations and the telecontrol server
are established in the master station. The telecontrol server forwards the messages
between the stations.
– Direct communication between stations ("GPRS direkt" mode)
The CP requires a fixed IP address to be assigned by the GSM network provider.