Dimensions - Wolf CGU-2-18 Installation And Maintenance Instructions Manual

Wall mounted gas fired combi boilers and wall mounted gas fired boilers with integral cylinder connection
Hide thumbs Also See for CGU-2-18:
Table of Contents

Advertisement

344
1 2
120
176
440
6

Dimensions

4
3
5
170
1
2
3
4
5
Installation inside a cupboard
For installation of the gas fired boiler inside a cupboard
note the following:
>25
- Removing the rear wall of the cupboard
Minimum lateral clearance between the gas fired boiler
and the cupboard sides 25 mm.
(CGG-2)
190
(CGU-2)
226
2
1
3
4
5
73
134
Gas fired combi
boilers
Heating flow
DHW
Cold water
Heating return
Gas connection
Never install the gas fired boiler on the back wall
of the cupboard, as it may not be substantial
enough to take the boiler's weight. This would
create the risk of water and gas leaks which in
turn would result in a risk of explosion
and flooding.
A cutout of 410 x 550 mm is required in the
cupboard top. Otherwise there is a risk of
suffocation and poisoning
With open flue gas fired boilers the
ventilation grill in the cupboard door must
be installed with a free minimum diameter
of 600 cm
2
Otherwise there is a risk of suffocation
and poisoning
393
Gas fired boilers
Heating flow
DHW flow
DHW return
Heating return
Gas connection
3062347_0309