1.3.3.5 High evaporator coil temp.T2 protection:
For 12K models:
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
For other models:T2>60℃, the compressor will stop and restart when T2≤54℃.
1.3.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30℃.
In auto mode, the machine will choose cooling, heating or fan-only mode according to ∆T (∆T =T1-Ts).
For 12K models:
For other models:
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
Electrical Control System
T2
TEstop
TEdown
TEnorm
∆T=T1-Ts
∆T>1℃
-1<∆T≤1℃
∆T≤-1℃
∆T=T1-Ts
∆T≥2℃
-1≤∆T<2℃
∆T<-1℃
Off
Decrease
Hold
Resume
Running mode
Cooling
Fan-only
Heating
Running mode
Cooling
Fan-only
Heating
Electrical Control Function