Leak Detection; Evacuation; Recharging Liquid Refrigerant; Characteristics Of R-410A - Carrier 61WG 020 Installation, Operation And Maintenance Instructions

Pro-dialog water-cooled/condenserless liquid chillers/water-sourced heat pumps with or without integrated hydronic module
Table of Contents

Advertisement

Before opening a refrigerant circuit, purge the circuit and
consult the pressure gauges.
Change the refrigerant after an equipment failure, following
a procedure such as the one described in NF E29-795 or carry
out a refrigerant analysis in a specialist laboratory.
If the refrigerant circuit remains open for longer than a day
after an intervention (such as a component replacement),
the openings must be plugged and the circuit must be charged
with nitrogen (inertia principle). The objective is to prevent
penetration of atmospheric humidity and the resulting
corrosion on the internal walls and on unpro-tected steel
surfaces.

19.5 - Leak detection

Never use oxygen or dry air, as this would cause a risk of fire
or explosion.
Carry out a leak detection test on the whole system using
the following methods: pressure test using dehydrated
nitrogen or a mixture of nitrogen and refrigerant used
for the system, helium leak test.
Connect the compressor to the system by opening the
valves.
The duration of the test must be sufficient to guaran-tee
the absence of very small leaks in the circuit.
Use specific tools, designed for leak detection.
The low-pressure side test pressure must not exceed
pressure Ps indicated on the compressor and unit name
plates.
If there is a leak, repair it and carry out the leak detec-tion
test again.

19.6 - Evacuation

To evacuate the system, observe the following recommen-
dations:
Connect the vacuum pump to the high (HP) and low-pressure
(LP) side for evacuation of the complete circuit. Never use
the compressor as a vaccum pump.
All units are equipped with valves with 3/8" SAE connections
on the suction, discharge and liquid lines, permitting the
connection of large-diameter flexible pipes limiting the
pressure drops for the evacuation.
1.
The vacuum level achieved must be 0.67 mbar (500 µm
Hg).
2.
Wait 30 minutes.
3.
If the pressure increases rapidly, the system ist not leak-
tight. Localise and repair the leaks. Restart the evacuation
procedure and repeat steps 1, 2, etc.
4.
If the pressure increeases slowly, this indicates that
moisture is present inside the system. Break the vacuum
with nitrogen and restart the evacuation procedure (steps
1, 2, etc.).
5.
Repeat the evacuation procedure (steps 1, 2); a vacuum
level of 0.67 mbar (500 µm Hg) must be achieved and
maintained for four hours.
This vacuum level must be measured at one of the system
connections and not at the vacuum pump pressure gauge.
50
ATTENTION: Do not use a megohmmeter and do not place
any stress on the compressor motor when the system has
been evacuated. There is a risk of internal short circuits
between the motor windings.
Do not use additives for leak detection. Do not use CFCs/
HCFCs as tracer fluids for leak detection.

19.7 - Recharging liquid refrigerant

CAUTION: The units are charged with liquid R-410A
refrigerant.
With high-pressure R-410A refrigerant the unit operating
pressure is above 4000 kPa (40 bar), the pressure at 35 °C air
temperature is 50% higher than for R-22. Special equipment
must be used when working on the refrigerant circuit
(pressure gauge, charge transfer, etc.).
All checks must be pressure tests, and the appropriate
pressure/temperature ratio table must be used to determine
the corresponding saturated temperatures (saturated bubble
point curve or saturated dew point curve).
Leak detection is especially important for units charged
with refrigerant R-410A. Depending on whether the leak
occurs in the liquid or in the vapour phase, the proportion
of the different components in the remaining liquid is not
the same.
NOTE: Regularly carry out leak checks and immediately
repair any leak found.

19.8 - Characteristics of R-410A

Saturated temperatures (°C) based on the relative pressure (in kPa)
Satur.
Relative
Satur.
Relative
temp.
pressure
temp.
pressure
-20
4
297
807
-19
312
5
835
-18
6
328
864
-17
345
7
894
-16
361
8
924
-15
9
379
956
-14
397
10
987
-13
415
11
1020
-12
12
434
1053
-11
453
13
1087
-10
473
14
1121
-9
15
493
1156
-8
514
16
1192
-7
535
17
1229
-6
18
557
1267
-5
579
19
1305
-4
20
602
1344
-3
21
626
1384
-2
650
22
1425
-1
23
674
1467
0
700
24
1509
1
726
26
1596
2
25
752
1552
3
779
27
1641
Satur.
Relative
Satur.
Relative
temp.
pressure
temp.
pressure
28
52
1687
3088
29
1734
53
3161
30
54
1781
3234
31
1830
55
3310
32
1880
56
3386
33
57
1930
3464
34
1981
58
3543
35
2034
59
3624
36
60
2087
3706
37
2142
61
3789
38
2197
62
3874
39
63
2253
3961
40
2311
64
4049
41
2369
65
4138
42
66
2429
4229
43
2490
67
4322
44
68
2551
4416
45
69
2614
4512
46
2678
70
4610
47
2744
48
2810
49
2878
50
2947
51
3017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents