B.4 MEMORY MAPPING
Value
Description
12
U6/AC5..7
13
U7/AC1..3
14
U7/AC5..7
15
U8/AC1..3
16
U8/AC5..7
B
F248
ENUMERATION: BRICK AUX BANK ORIGIN
Value
Description
0
None
1
U1/AC4
2
U1/AC8
3
U2/AC4
4
U2/AC8
5
U3/AC4
6
U3/AC8
7
U4/AC4
8
U4/AC8
9
U5/AC4
10
U5/AC8
11
U6/AC4
12
U6/AC8
13
U7/AC5
14
U7/AC8
15
U8/AC5
16
U8/AC8
F253
ENUMERATION: BRICK TRANSDUCER ORIGIN
Value
Description
0
None
1
U1/DC1
2
U1/DC2
3
U1/DC3
4
U2/DC1
...
...
24
U8/DC3
F254
ENUMERATION: INCIPIENT CABLE FAULT MODE
Value
Function
0
Number of Counts
1
Counts per Window
F256
ENUMERATION: BRICK ORIGIN/DESTINATION
Value
Description
0
None
B-80
Value
1
2
3
4
5
6
7
8
F259
ENUMERATION: BRICK RTD TYPE
0 = 100 Ohm Nickel, 1 = 120 Ohm Nickel, 2 = 100 Ohm Platinum
F260
ENUMERATION: DATA LOGGER MODE
0 = Continuous, 1 = Trigger
F261
ENUMERATION: BANK REDUNDANCY TYPE
0 = None, 1 = Dependability Biased, 2 = Security Biased
F262
ENUMERATION: BRICK STATUS
0 = Disabled, 1 = OK, 2 = Communications Trouble, 3 = Equip-
ment Mismatch, 4 = Brick Trouble
F270
ENUMERATION: FAULT REPORT VT SUBSTITUTION
Value
0
1
2
F300
UR_UINT16: FLEXLOGIC™ BASE TYPE (7-bit type)
The FlexLogic™ BASE type is 7 bits and is combined with an 8-bit
descriptor and 1 bit for protection element to form a 16-bit value.
The combined bits are of the form: PTTTTTTTDDDDDDDD,
where P bit if set, indicates that the FlexLogic™ type is associated
with a protection element state and T represents bits for the BASE
type, and D represents bits for the descriptor.
The values in square brackets indicate the base type with P prefix
[PTTTTTTT] and the values in round brackets indicate the descrip-
tor range. The right-most T bit indicates whether the type is an ON
or OFF type. There can be a total of 64 types (plus protection ele-
ments). There can be a total of 256 descriptors of each type.
[0] Off(0) – this is boolean FALSE value
[0] On (1) – this is boolean TRUE value
[2] CONTACT INPUTS (1 to 96)
[3] CONTACT INPUTS OFF (1 to 96)
[4] VIRTUAL INPUTS (1 to 32)
F35 Multiple Feeder Protection System
Description
U1
U2
U3
U4
U5
U6
U7
U8
Description
None
I_0
V_0