GE F35 Instruction Manual page 263

Multiple feeder protection system, ur series
Hide thumbs Also See for F35:
Table of Contents

Advertisement

5 SETTINGS
The undervoltage delay setting defines the family of curves shown below.
where: T = operating time
D = undervoltage delay setting (D = 0.00 operates instantaneously)
V = secondary voltage applied to the relay
V
= pickup level
pickup
At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting.
NOTE
GE Multilin
D
T
--------------------------------- -
=
V
1
------------------
V
pickup
% of voltage pickup
Figure 5–57: INVERSE TIME UNDERVOLTAGE CURVES
F35 Multiple Feeder Protection System
5.6 GROUPED ELEMENTS
842788A1.CDR
(EQ 5.19)
5
5-127

Advertisement

Table of Contents
loading

Table of Contents