Programmable input (Reset)

There is a programmable input that can have several alternate
functions. As a factory default it is configured as a Reset input that
will reset all alarms and relays. It is intended to be switched using
volt free contacts that are normally open. Leave the input open
circuit if not used.
ID Indicator
1 ALARM
2 PREALARM
3 SMOKE LEVEL
4 INITIALISATION
5
FAULT
6 POWER
7
POWER FAULT
8 AIR FLOW
LOW FLOW
SENSOR
ASPIRATOR
DRIFT COMPENSATION
9
TEMPERATURE (b)
INPUT (a)
DISABLE
SYSTEM
SOUNDER
FILTER
HIGH FLOW
Table 1A: Stand-alone device
Meaning
Colour
Action
Red
ON
Channel in Fire Alarm
Green
Blink
Sensor poll
Yellow
ON
Channel is in pre‐alarm
Yellow
ON
Shows alarm level reached
Yellow
ON
Device is initialising
Yellow
ON
Device has one or more troubles
Yellow
Blink
Fault delay in progress
Red
Blink
Test button pressed
Green
ON
Power on device
Red
Blink
Reset button pressed
Yellow
ON
Lo/Hi voltage range warning
Yellow
Blink
Power restart alert
Red
Blink
Disable button pressed
Green
ON
Centre OK; left low; right high
Yellow
Blink
Fault delay in progress
Yellow
ON
Low air flow problem
Yellow
Blink
Sensor initialisation problem
Yellow
Double blink
Sensor communications problem
Yellow
ON
Air flow monitoring problem
Yellow
Blink
Air flow initialisation problem
Yellow
Double blink
Fan problem
Yellow
Blink
Sensor drift, alert 1
Yellow
Double blink
Sensor drift, alert 2
Yellow
Triple blink
Sensor drift limit warning
Yellow
Blink
Low temperature alert
Yellow
Double blink
High temperature alert
Yellow
Blink
External input problem
Yellow
Blink
No alarms or problems reported
Yellow
Blink
Error in device configuration
Yellow
Double blink
EEPROM problem
Yellow
Triple blink
Real Time Clock problem
Yellow
Blink
Sounder problem
Yellow
Blink
Filter cleaning date is reached
Yellow
Blink
Fault delay in progress
Yellow
ON
High air flow problem
(For position of the indicators (ID) on the front panel, see Figure 2A)
FRONT PANEL LEDS – WHAT THEY SHOW
The front panel indicators use the following colour convention:
Green
Red
Yellow
For simultaneous faults/alerts on the same LED, the priority order is:
ON (highest) > blink > double blink > triple blink (lowest)
The meaning of all the front panel indicators are detailed in Tables
1A and 1B below:
To test if all the front panel LEDs are functioning, hold the TEST
button while the device is powered on. The firmware version
number will be displayed for 2 seconds on the Channel 1 smoke
level LEDs and then the front panel LEDs are illuminated, in the
following sequence: all the red LEDs, all the yellow LEDs, all the
green LEDs.
Notes
Fire relay is set
In normal operation
Pre‐alarm relay is set
Numbers 1‐9 only used for smoke density
Takes about 3 minutes
Relay set; general fault is not latched as default
Default is 60s; fault relay is set at end of delay
Check PSU wiring and voltage
Disabled as default
Ch1 upper row; Ch2 lower row
Default is 60s; general fault set at end of delay
Check filter and pipes for blockages
Restart device; change sensor
Check sensor address; change sensor
Restart device; run diagnostic
Check filter and pipes for blockages; try restart.
Try device restart.
Clean sensor
Clean sensor
Clean sensor ‐ urgent
Check air temperature
Check air temperature
Blinks Green when set as RESET input (default)
Returns to normal mode after 60 min (default).
Flashes all FAULT LEDs; try device restart
Check PSU voltage; try device restart
RTC is corrupted or internal power failed
Check EOL and sounder circuit
Set a valid future date
Default is 60s; general fault set at end of delay
Check pipes for breaks and leaks
2
OK
Alarm
Trouble
Hor03-01