JADAC Power Support
3.3
Transferring load to static bypass
Confirm: "No Active Alarms" is displayed.
On Display Select:
3.4
Manual bypass (detour)
Perform Load on Static Bypass procedure.
Close Manual Bypass (CB3).
Open Load Output Isolator (SW1).
Open Rectifier Input (CB1).
Open Reserve Input (CB2).
Open Battery Fuses.
The unit will be safe to work on once the display has switched off.
3300 UPS Manual