JADAC Power Support
2.0

INSTALLATION

2.1

Installation precautions

The following factors should be considered to determine a suitable location for your
unit:
• Protection against excessive temperature and humidity
• Protection against moisture
• Ease of access and adequate lighting for service personnel
• It's position relative to the critical load for ease of reticulation
• Adequate ventilation clearance (rear end)
• A close proximity of the UPS to the battery cabinet where applicable
• Potential expansion, e.g. additional battery cabinet/unit
2.2

General

The unit requires access from the front, top and from one side so care should be
taken in positioning the unit accordingly.
2.3

Cable and circuit breaker ratings

The recommended input, output cable and circuit breaker sizes are listed in the
table below. The input circuit breaker must have a D curve response and should
be mounted in the existing DB board. The UPS supply must not be connected via
an earth leakage breaker.
kVA
Input
Rating
Current
10
15
20
30
40
All input and output cables should have four cores plus an earth respectively
2.4

Wiring layout and connections

The cable entry for the unit is at the rear behind a removable cover-plate.
Always ensure that all the cables are secure and the length adequate.
The terminal block layout and wiring numbering is shown on the next page.
It can bee seen that the reserve and rectifier terminals are bridged.
If it is required to supply the unit from two different sources, simply remove the
bridging cables. The phase rotation must always be clockwise.
The labeling notation is as follows:
Rectifier input terminals:
Reserve input terminals:
Output terminals:
The earth connection is made to the earth stud under the wiring compartment.
Circuit
Breaker
32A
40A
32A
40A
32A
40A
63A
80A
63A
80A
Input Cable
2
10mm
2
10mm
2
10mm
2
16mm
2
25mm
1U1, 1V1, 1W1 & 1N1
2U1, 2V1 & 2W1
U2, V2, W2 & N2
3300 UPS Manual
Output
Output
Current
Cable
15A
2.5mm
23A
4mm
30
6mm
45
10mm
60
16mm
Page 5 of 24
2
2
2
2
2