Summary of Contents for Kaco proLOG M

  • Page 1 Operator’s Manual Installation Instructions KACO-proLOG M / XL...
  • Page 2: Table Of Contents

    4.4.7 D0 digital output 4.4.8 Analog / digital inputs 4.5 Pin allocation 5 Start-up 5.1 Start-up / login of KACO-proLOG via PVI-web 7 5.2 Procedure 5.3 KACO-proLOG XL display menu and Status LEDs 7 5.3.1 Description of the 4 Status LEDs: 5.3.2 Display menu...
  • Page 3: About This Document

    However, INVitten damage reports must be 1.4 UL Certification received by the forwarding agent within six days after CE labeling is used to document that the KACO receipt of the goods at the latest. proLOG data logger indicated on the type label meets...
  • Page 4: Notes Concerning Installation And Operation

    Operation 4.2 Installation of the data logger 3.1 Factory guarantee and liability KACO SOLAR INC. grants a guarantee of two years on The device is suitable for wall installation. The KACO-proLOG, starting from the date of installation. boreholes can be marked as shown in the sketch below.
  • Page 5: Connections

    The RS485 is internally bridged from the PVI-go port to 4.4.3 Telephone the “B A RS485“ terminal. KACO and PVI inverters can now be operated together. The data loggers are equipped with an internal modem (analog or ISDN). The 24V internal <->...
  • Page 6: D0 Digital Output

    To configure this function you must connect to Signal KACO-proLOG and make the necessary adjustments via the browser (Admin Monitoring -> switch output). The output has been designed as an optocoupler output (make contact); so external voltage must be applied as necessary.
  • Page 7: Pin Allocation

    More detailed instructions are given in Section 7.2, “online data.” 5 Start-up 5.3 KACO-proLOG XL display menu and Status 5.1 Start-up / login of KACO-proLOG via PVI-web LEDs On-site configuration of the data logger is 5.3.1 Description of the 4 Status LEDs: NOT necessary .
  • Page 8: Display Menu

    Up arrow – select a menu point above the current row; increase value Down arrow: Select a menu point below the current row; reduce value Escape: Abort your entry or return to the previous menu level KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 9: Structure Of The Display Menu

    5.3.3 Structure of the display menu KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 10 (unless another mask is assigned by the BOOTP or DHCP server) Gateway: Indicates the gateway being used (unless another assignment has been made) Modem/ISDN/GSM Local IP address: Defines the IP address of KACO-proLOG in the WAN. KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 11 Total energy yield Alarms/errors Communication: Error during modem connection buildup System: A system error has occurred. Measuring channels: Error during the detection of measuring channels. Set pasword as 0030 to use a KACO- web plant. KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 12: Kaco-Prolog M, L Led Menu

    5.4 KACO-proLOG M, L LED menu Instead of a display, KACO-proLOG M and L use LEDs to indicate the condition of the device. How to navigate within this menu is showing below: Description of LEDs in the “Communications“ submenu No Dialtone – the device is unable to receive an external exchange line.
  • Page 13: Connection Buildup

    A table showing the possible connections is shown on page 35. Hardware Standard PC with modem (analog or ISDN) for KACO- proLOG with modem, or Ethernet network connection for KACO-proLOG with Ethernet connection, enabling email data transfer via the network.
  • Page 14: Windows 95/98

    (A suitable modem must be connected to your PC and installed). If KACO-proLOG is equipped with an internal analog modem, an analog modem or ISDN modem with analog simulation must be used for communication.
  • Page 15 After establishing the connection the browser is opened (e.g. Netscape 6.1) and the IP address of the device is entered. The standard address is: http://192.168.200.1. Confirm this address to access to the start page of KACO-proLOG. KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 16: Windows 2000

    In addition, enter the modem you wish to use for this connection. (A suitable modem must be connected to your PC and installed). If KACO-proLOG is equipped with an internal analog modem, an analog modem or ISDN modem with analog simulation must be used for communication.
  • Page 17 (wait until externall call prefix is established). More detailed information is given in the description of the telephone system In the dialog “Connect to KACO-proLOG”, click (Features) to open another window. Highlight [Internetprotokoll (TCP/IP)] click (Features).
  • Page 18: Windows Xp

    (e.g. Netscape 6.1) and the IP address of the ” Connect to remote data transfer modem “. device entered. standard address http://192.168.200.1. Confirm this address to access the start page of KACO- proLOG. KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 19 This name will be used to enable your connection again later. In the next dialog, enter the phone number of KACO-proLOG. The next dialog can be used to enter a user name of your choice under “User “. The “Password” fields may remain blank.
  • Page 20 “Admin” must be entered as the user name and password. Please note that an external call prefix may be necessary when entering the telephone number. In most cases, this external call prefix will be assigned a preceding “0”. KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 21: Kaco - Web (Optional)

    After successful buildup of the connection the browser is opened (e.g. Netscape 6.1) and the IP address of the device is entered. The standard address is: http://192.168.200.1. Confirm this address to access the start page of KACO- proLOG. KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 22: Menu Description

    7 Menu description After the DFÜ (remote data transfer) or network connection has been established successfully, you can now access the menu structure of KACO-proLOG via a browser. If you use a DFÜ connection (modem), enter http://192.168.200.1/ your browser. If you use a network connection, enter the IP address (standard: http://192.168.100.50/) in your browser.
  • Page 23: Online Values

    Total energy yield 0.000 Example: The plant consists of two sub-sections which have separate meters connected to KACO-proLOG. To obtain correct sums you must activate these two separate meters under “Admin – Measurement” -> Energy – Digital Channels”. Details of digital inputs:...
  • Page 24: Current Sensors

    7.3 Status 7.2.2 Current sensors 7.3.1 Plant messages If current sensors (KACO-go) are connected, the current measuring values of these current sensors will This menu item provides a summary of possible alarm be displayed in this field. statuses. Measured value alarms are returned as a result of the criteria predefined under “Admin –...
  • Page 25: Inverters

    More detailed information is given on the next page. • Bell signal (analog modem): Defines the number of bell signals until KACO- proLOG responds • Contact for daily file transfer via fax: Daily files can additionally be sent by fax at a defined hour.
  • Page 26: Standard Contact

    Changes will only be active after pressing 7.4.2 Standard contact the “Save” button. When KACO-proLOG is preset, all alarm messages and read value files are sent to the address entered under “standard contact.” Changes may be entered for the individual alarm criteria, plant messages, or plant parameters.
  • Page 27: Admin - Monitoring

    Changes will not be active until the “Save” The ISDN Terminal adapter settings refer to the ISDN button is pressed. settings of KACO-proLOG. If the device is to be used at an ISDN extension you must enter the appropriate 3. Email extension number.
  • Page 28: Contact Addresses

    Dialling code(s) SMS server code(s), separated by semicolon. Collective email address KACO offers a service which sends emails via the Phone number SMSC (analog) server of the computer center. Server telephone number which is used when sending To use this server, enter the collective email address: SMS.
  • Page 29: Switching Output

    This pulse constant indicates how many pulses KACO-proLOG will output for one kilowatt hour of energy produced at D0. If the output is used as an alarm output, i.e. for the 7.5.5 Inverters...
  • Page 30: Status Alarms

    The following functions are differentiated under Formula Settings: Analog: If a defined limit value is exceeded, the message will be sent to the contact defined under Settings (e.g. Measur. Channel 1 >= limit of 8.0 V). KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 31: Digital Channels

    This field is used to add or delete sensors. To do this, enter the bus address into the field and click “Add” or “Delete”. After completing your entries, click “Accept” to confirm and accept the new list of addresses. KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 32: Sample Configuration

    As the temperature is to be measured up to –50°C, an alarm message to report a defect or malfunction it follows that the offset is: within the plant. = 50 − ° Offset KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 33: Parameterization Of The Measuring Device

    To gain more freedom and flexibility when selecting a range, two different gradients can be defined. c (upper limit) The shift of the straight line by t and t is to be upper lower defined as an absolute value (e.g.: 0.2kW). KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 34: Programming Criteria Based On The Example Of An Inverter Comparison

    Then enter if you wish to calculate limits can be set under item c; the gradient is set under the criterion at each logging interval or once per day. item m. The gradient may remain unchanged in most cases. KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 35: List Of Abbreviations

    AC voltage Plant Section 3 U_AC_3 Wind speed W_V0 Wind direction W_R0 ° Air humidity F_L0 Quantity of heat - Collector WM_K0 Quantity of heat - Heating WM_H0 Quantity of heat – Cogeneration Plant WM_BHKW0 KACO SOLAR INC. Operator’s Instructions KACO-proLOG...
  • Page 36: Technical Data

    Alarm options of the various modem types: Ethernet Alarm via email Direct connection to the PC only possible via network card. ISDN Alarm via email, sms Direct connection to the PC only possible via ISDN modem. KACO SOLAR INC. Operator’s Instructions KACO-proLOG...