GE 345 Communications Manual page 55

Transformer protection system transformer protection and control
Hide thumbs Also See for 345:
Table of Contents

Advertisement

CHAPTER 1: COMMUNICATIONS GUIDE
345 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
⊠ Two octets (with originator address). Originator address is set to zero if not used.
7.
Maximum length of APDU.
253 in both directions (the maximum length is a fixed system parameter).
8.
Selection of standard ASDUs.
For the following lists, the boxes indicate the following: ⊠ – used in standard direction;
□ – not used.
Process information in monitor direction:
Table 19: Process information in monitor direction
Number / description
⊠ <1> := Single-point information
□ <3> := Double-point information
□ <5> := Step position information
□ <7> := Bitstring of 32 bits
□ <9> := Measured value, normalized value
⊠ <11> := Measured value, scaled value
□ <13> := Measured value, short floating point value
⊠ <15> := Integrated totals
□ <20> := Packed single-point information with status change detection
□ <21> := Measured value, normalized value without quantity descriptor
⊠ <30> := Single-point information with time tag CP56Time2a
□ <31> := Double-point information with time tag CP56Time2a
□ <32> := Step position information with time tag CP56Time2a
□ <33> := Bitstring of 32 bits with time tag CP56Time2a
□ <34> := Measured value, normalized value with time tag CP56Time2a
⊠ <35> := Measured value, scaled value with time tag CP56Time2a
□ <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
⊠ <37> := Integrated totals with time tag CP56Time2a
□ <38> := Event of protection equipment with time tag CP56Time2a
□ <39> := Packed start events of protection equipment with time tag
CP56Time2a
□ <40> := Packed output circuit information of protection equipment with time
tag CP56Time2a
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>,
and <19> or of the set <30> to <40> are used.
ETHERNET INTERFACE
Mnemonic
M_SP_NA_1
M_DP_NA_1
M_ST_NA_1
M_BO_NA_1
M_ME_NA_1
M_ME_NB_1
M_ME_NC_1
M_IT_NA_1
M_SP_NA_1
M_ME_ND_1
M_SP_TB_1
M_DP_TB_1
M_ST_TB_1
M_BO_TB_1
M_ME_TD_1
M_ME_TE_1
M_IT_TB_1
M_EP_TD_1
M_EP_TE_1
M_EP_TF_1
1–51