GE 345 Communications Manual page 37

Transformer protection system transformer protection and control
Hide thumbs Also See for 345:
Table of Contents

Advertisement

CHAPTER 1: COMMUNICATIONS GUIDE
345 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
This is a function used to quickly read the status of a selected device. A short message
length allows for rapid reading of status. The status byte returned will have individual bits
set to 1 or 0 depending on the status of the slave device. For this example, consider the
following 350 general status byte:
The master/slave packets have the following format:
Mask
0x01
0x02
0x04
0x08
0x10
0x20
0x40
0x80
Query:
Field Name
Slave Address
Function
Response:
Field Name
Slave Address
Function
Device Status (see definition above)
08H Diagnostics
Just respond, no action required for now.
Serves as a loopback test.
Outgoing message for this function is the same as input one.
16 (10 Hex) Preset Multiple Registers
Presets values into a sequence of holding registers (4X references.
Query:
The query message specifies the register references to be preset. Registers are addressed
starting at zero: register 1 is addressed as 0.
The requested preset values are specified in the query data field. Data is packed as two
bytes per register.
Here is an example of a request to preset two registers starting at 43851 to 00 01 and 00
00 hex, in slave device 254:
Function
Alarm
Trip
Self Test Fault
Breaker Connected
52a Status
52b Status
Maintenance
In Service
Hex
FE
07
Hex
FE
07
2C
ETHERNET INTERFACE
1–33

Advertisement

Table of Contents
loading

Table of Contents