Safety Considerations; System Requirements - Carrier 38GXM series Installation Instructions Manual

Multi-split high-wall duct free split system
Hide thumbs Also See for 38GXM series:
Table of Contents

Advertisement

SAFETY
CONSIDERATIONS
Installing,
starting
up, and servicing
air-conditioning
equipment
can be hazardous
due to system
pressures,
electrical
components,
and equipment
location
(roofs,
elevated
structures,
etc.).
Only
trained,
qualified
installers
and service
mechanics
should
install, start-up,
and service this equipment.
Untrained
personnel
can perform
basic maintenance
flmctions
such
as cleaning
coils. All other
operations
should
be performed
by
trained
service personnel.
When
working
on the
equipment,
observe
precautions
in the
literature
and
on
tags,
stickers,
and
labels
attached
to
the
equipment.
Follow
all safety codes. Wear safety glasses and work gloves.
Keep
quenching
cloth and fire extinguisher
nearby
when
brazing.
Use
care in handling,
rigging,
and setting bulky
equipment.
Read
these
instructions
thoroughly
and follow
all warnings
or
cautions
included
in literature
and
attached to the unit.
Consult
local building
codes and current editions
of the National
Electrical
Code ( NEC ) NFPA 70. In Canada,
refer to current editions
of the
Canadian
electrical
code CSA 22.1.
Recognize
safety information.
This is the safety-alert
symbol/}k
.
When
you
see this
symbol
on the unit
and in instructions
or
manuals,
be alert to the potential
for personal
injury.Understand
these
signal
words:
DANGER,
WARNING,
and
CAUTION.
These
words
are used
with
the
safety-alert
symbol.
DANGER
identifies
the
most
serious
hazards
which
will result
in severe
personal
injury
or death.
WARNING
signifies
hazards
which
could
result
in personal
injury
or death.
CAUTION
is used to
identify
unsafe practices
which may result in nfinor personal
injury
or product
and property
damage.
NOTE
is used
to highlight
suggestions
which will result in enhanced
installation,
reliability,
or
operation.
ELECTRICALSHOCK
HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical
disconnect
switch
must
be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
EQUIPMENT
DAMAGE HAZARD
Failure to follow
this caution may result in equipment
damage or improper operation.
Do not bury more than 36 in. (914 ram) of refrigerant pipe
in the ground. If any section of pipe is buried, there must be
a 6 in. (152 ram) vertical rise to the valve connections on
the outdoor units. If more than the recommended
length is
buried, refrigerant may nfigrate to the cooler buried section
during extended periods of system shutdown. This causes
refrigerant
slugging
and
could
possibly
damage
the
compressor at start-up.
GENERAL
These instructions cover the installation, start-up and servicing of
the 38GXM outdoor unit connected to up to four 40GXM indoor
high wall units.
For approved combinations,
please refer to the
Product Data.
SYSTEM
REQUIREMENTS
Allow
sufficient
space
for airflow
and servicing
unit.
See Fig. 2
and 3 for minimum
required
clearances.
IMPORTANT:
Both
refrigerant
lines
must
be
insulated
separately.
• Minimum
refrigerant
line length between
the indoor
and outdoor
units is 10 ft. (3 m).
The following
maximum
lengths
are allowed:
REFRIGERANT LINE LENGTHSR (m)
Unit Size
18 K
24 K
30 K
Total Piping
124 (38)
124 (38)
230 (70)
Max Pipe Length to Any One
82 (25)
82 (25)
82 (25)
FCU
Max Elevation (ID over OD)
49 (15)
Max Elevation (OD over ID)
33 (10)
The following
are the piping sizes.
UNIT SERVICE VALVESIZE*
Unit Size
Mix Phase
Vapor
18 & 30 K
1/4"
3/8"
24 K
1/4"
1/2"
Unit can have 2 or 4 service valves with the same pipe sizes
CONVERSION JOINTS
Model
Qty. and
When Used
Type
lx
38GXM218---3
(3/8 to 1/2)
Connecting Size 12 K FCU
2x
38GXM224---3
(1/2
to 3/8)
Connecting
Size 9 K FCU
3 x
Connecting Size 12
38GXM430---3
(3/8 to 1/2)
or 18 K FCU
Refrigerant
Charge
REFRIGERANTCHARGE
Charge Weight lb. (kg)
3.5
(1.6)
5.5 (2.5)
7.3 (3.3)
Unit Size
18K
24 K
30 K
Above
charge is for piping
runs up to 50 ft. (15 m) per system
for sizes 18 and 24 and 100 fl (30 m) per system for size 30.
• For piping
runs
greater than those listed above,
add 0.23 oz
for size 18, 0.17 oz for size 24, and 0.54 oz for size 30 of
refrigerant
per foot of extra piping
up to the allowable
length.
• Electronic
expansion
valves in the outdoor
unit are used as
metering
devices.
Connecting
(Power
and Control
Cable)
• The main power
is supplied
to the outdoor
unit.
The field
supplied
connecting
cable from the outdoor
unit to indoor
unit
consists
of four wires and provides
the power
for the indoor
unit
as well as the communication
signal and ground between
the
outdoor
and indoor
unit.
Two wires are high voltage
AC power, one is high voltage
controls
and one is a ground wire.
• Consult local building
codes, NEC (National
Electrical
Code) or
CEC (Canadian
Electrical
Code)
for special
requirements.
MIN. CKT AMP
UNIT SIZE
POWER SOURCE
MAX FUSE/CB
AMP
18k
208/230-1-60
14/20
24k
208/230-1-60
20/30
30k
208/230-1-60
24/40
Connecting
Cable:
Voltage drop on the connecting
cable
should be kept to a minimum.
Do not use thermostat
wire,
Use minimum
14AWG 4 conductor
cable (solid or stranded).

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

40gxm series

Table of Contents