Electrical Data; Recommended Fuse And Cable Sizes - McQuay AC20C / MAC020C Installation Manual

Air cooled chiller c series
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Table B-1 : ( R407C - Cooling Only )
Model
Power supply
Voltage range
Nominal Power Input
Nominal Current Input
Maximum Continuous Current
Full Load Current (FLA)
Locked Rotor Current (LRA)
Pump Power Input
Table B-2 : ( R22 - Cooling Only )
Model
Power supply
Voltage range
Nominal Power Input
Nominal Current Input
Maximum Continuous Current
Full Load Current (FLA)
Locked Rotor Current (LRA)
Pump Power Input
Table B-3 : ( R407C - Heatpump )
Model
Power supply
Voltage range
Nominal Power Input (Cooling/Heating) kW
Nominal Current Input (Cooling/Heating) A
Maximum Continuous Current
Full Load Current (FLA)
Locked Rotor Current (LRA)
Pump Power Input (Cooling/Heating)
Table B-4 : ( R22 - Heatpump )
Model
Power supply
Voltage range
Nominal Power Input (Cooling/Heating) kW
Nominal Current Input (Cooling/Heating) A
Maximum Continuous Current
Full Load Current (FLA)
Locked Rotor Current (LRA)
Pump Power Input (Cooling / Heating)
Cooling / Heat Pump
Model
Voltage Range **
Recommended Fuse *
Power Supply Cable Size *
Number of Conductor
Interconnection Cable Size *
IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected to comply with
the local/national codes of regulations. This is also subjected to the type of installation and conductors used.
** The appropriate voltage range should be checked with label data on the unit.
All field wiring must be installed in accordance with the national wiring regulation.
All the terminals and connections must be tightened. Improper connection and fastenings could cause electric shock, short
circuit and fire.
Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to
the wiring diagram.
The unit must be GROUNDED to prevent possible hazards due to insulation failure.
All electrical wiring must not touch the refrigerant piping, compressor, pump, fan motor or any moving parts of the fan
motors.
Do not operate the chiller with wet hands. It would result in electric shock.
Do not use fuse of different amperage than stated. Using wire etc. to replace a fuse could cause equipment damage or fire.

ELECTRICAL DATA

4AC20C
V-ph-Hz
V
kW
2.62
A
12.70
A
18.3
A
14
A
57
W
183
AC20C
V-ph-Hz
V
kW
2.68
A
12.64
A
18.3
A
14
A
57
W
175
4AC20CR
V-ph-Hz
V
2.61/2.69
12.69/12.99
A
18.3
A
14
A
57
W
173/181
AC20CR
V-ph-Hz
V
2.61/2.70
12.38/12.73
A
18.3
A
14
A
57
W
175/186

RECOMMENDED FUSE AND CABLE SIZES

4AC20C/CR
4AC25C/CR
AC20C/CR
AC25C/CR
220 ~ 240V /1Ph /50Hz + N + !
A
27
mm
2
10
3
2
mm
1.5
1.5
! ! ! ! ! CAUTION
1-8
4AC25C
4AC30C
4AC40C
230 / 1 / 50
220 - 240
2.96
3.69
13.59
17.48
23
27
17.5
22.5
82
114
189
199
AC25C
AC30C
AC40C
230 / 1 / 50
220 - 240
2.74
3.50
12.11
16.70
23
27
16.5
21.4
82
114
190
201
4AC25CR
4AC30CR
4AC40CR
230 / 1 / 50
220 - 240
3.09/2.75
3.82/4.00
4.85/5.01
14.3/14.1
19.29/20.19
9.13/9.23
23
27
17.5
22.5
82
114
186/195
194/214
320/334
AC25CR
AC30CR
AC40CR
230 / 1 / 50
220 - 240
2.95/2.83
3.55/3.56
4.59/4.65
13.4/12.8
18.24/18.37
8.67/8.78
23
27
16.5
21.4
82
114
189/194
201/211
320/329
4AC30C/CR
4AC40C/CR
AC30C/CR
AC40C/CR
380 ~ 415V /3Ph /50Hz + N + !
38
45
22
10
10
5
3
3
5
1.5
1.5
4AC50C
4AC60C
400 / 3 / 50
380 - 415
4.94
5.97
6.88
9.29
10.22
12.93
14
14
17
12.4
11.8
14.3
65.5
74
101
320
345
349
AC50C
AC60C
400 / 3 / 50
380 - 415
4.50
5.26
6.38
8.80
9.30
12.32
14
14
17
10.5
11.3
12.3
65.5
74
101
320
345
351
4AC50CR 4AC60CR
400 / 3 / 50
380 - 415
5.47/5.66
6.53/6.28
9.59/9.96 12.77/12.67
14
14
17
12.4
11.8
14.3
65.5
74
101
336/347
347/358
AC50CR
AC60CR
400 / 3 / 50
380 - 415
5.07/5.01
6.57/6.26
8.99/8.95 13.49/13.03
14
14
17
10.5
11.3
12.3
65.5
74
101
336/349
351/357
4AC50C/CR
4AC60C/CR
AC50C/CR
AC60C/CR
24
29
5
5
5
5
1.5
1.5