WARNING
If NOT factory installed, a main switch or other
means for disconnection, having a contact
separation in all poles providing full
disconnection under overvoltage category III
condition, shall be installed in the fixed
WARNING
ONLY use copper wires.
Make sure the field wiring complies with the
applicable legislation.
All field wiring must be performed in
accordance with the wiring diagram supplied
with the product.
NEVER squeeze bundled cables and make
sure they do not come in contact with the
piping and sharp edges. Make sure no
external pressure is applied to the terminal
connections.
Make sure to install earth wiring. Do NOT
earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earth may
cause electrical shock.
Make sure to use a dedicated power circuit.
NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or
circuit breakers;
Make sure to install an earth leakage
protector. Failure to do so may cause electric
shock or fire.
When installing the earth leakage protector,
make sure it is compatible with the inverter
(resistant to high frequency electric noise) to
avoid unnecessary opening of the earth
leakage protector.
NOTICE
Precautions when laying power wiring:
Do not connect wiring of different thicknesses
to the power terminal block (slack in the power
wiring may cause abnorm al heat).
When connecting wiring which is the same
thickness, do as shown in the figure below.
For wiring, use the designated power wire
and connect firmly, then secure to prevent
outside pressure being exerted on the
terminal board.
Use an appropriate screwdriver for
tightening the terminal screws.
A screwdriver with a small head will
damage the head and make proper
tightening impossible.
Page 6
Install power cables at least 1 metre away from
televisions or radios to prevent interference. Depending
wiring.
on the radio waves, a distance of 1 metre may not be
sufficient.
Over-tightening the terminal screws may
break them.
WARNING
After finishing the electrical work, confirm
that each electrical component and terminal
inside the electrical components box is
connected securely.
Make sure all covers are closed before
starting up the unit.