Siemens RVP36 Installation Instructions Manual page 7

Heating controller for 2 heating circuits and d.h.w.
Table of Contents

Advertisement

Plant types 6-x
Function block "Plant configuration"
51 Plant type
Function block "Space heating"
61 Heating limit NORMAL
(ECO day)
62 Heating limit REDUCED
(ECO night)
63 Building time constant
64 Quick setback
65 Room temperature source
66 Type of optimization
67 Maximum heating up period
68 Maximum early shutdown
69 Maximum limitation of room
temperature
70 Influence of room
temperature (gain factor)
71 Boost of room temperature
setpoint on boost heating
Siemens Building Technologies
5-1
(4-0...6-1)
17.0 °C
(--- / –5.0...25.0)
5.0 °C
(--- / –5.0...25.0)
20 h
(0...50)
1
(0 / 1)
A
(0...3 / A)
0
(0 / 1)
0:00 h
(0:00...42:00)
0:00 h
(0:00...6:00)
--.- °C
(--.- / 0.0...35.0)
4
(0...20)
5 °C
(0...20)
74 319 0817 0 a
See the plant diagrams above
........................
°C
.................
--- = function deactivated
°C
.................
°C
.................
--- = function deactivated
°C
.................
10 h = light building construction
20 h = medium building construction
h
....................
50 h = heavy building construction
0 = without quick setback
........................
1 = with quick setback
........................
0 = no room sensor available
........................
1 = room unit connected to terminal A6
........................
2 = room sensor connected to terminal B5
3 = mean value of both devices connected to
terminals A6 and B5 (heating circuit 1)
and / or A6 and B52 (heating circuit 2)
A = automatic selection
0 = optimization with room model
........................
1 = optimization with room unit / room sensor
........................
(setting 0 only provides optimum start control)
h Maximum forward shift for switching on
.....................
h before occupancy starts
.....................
0:00 = no optimum start control
h Maximum forward shift for switching off
.....................
h before occupancy ends
.....................
0:00 = no optimum stop control
°C --- = limitation deactivated,
.................
°C function can only be provided with
.................
room unit / room sensor
Function can only be provided with
........................
room unit / room sensor
........................
°C
.................
°C
.................
CE1G2546en
28.02.2011
7/12