Inverter Powerful Operation - Daikin FLKS25BAVMB Service Manual

Inverter pair floor / ceiling suspended dual type flk(x)s-ba series
Hide thumbs Also See for FLKS25BAVMB:
Table of Contents

Advertisement

SiBE05-722EE
How to Set the Temperature and Airflow Rate
When using HOME LEAVE operation for the first time, set the temperature and airflow rate for
HOME LEAVE operation. Record your preferred temperature and airflow rate.
Cooling
Heating
1. Press the HOME LEAVE button.
2. Adjust the temperature with
3. Adjust the airflow rate with the FAN setting button as you like.
HOME LEAVE operation will run with these settings the next time you start HOME LEAVE
operation. To change the recorded information, repeat steps 1 – 3.
Others

1.10 Inverter POWERFUL Operation

Outline
In order to exploit the cooling and heating capacity to full extent, the air conditioner can be
operated by increasing the indoor fan rotating speed and the compressor frequency.
Detail
When the POWERFUL button is pressed, the fan speed and target temperature are converted
to the following states for 20 minutes.
Operation mode
COOL
DRY
HEAT
FAN
AUTO
A
Ex: POWERFUL operation in cooling
Note:
POWERFUL Operation cannot be used together with OUTDOOR UNIT QUIET Operation.
Functions and Control
Initial setting
Temperature
25°C
25°C
Make sure
is displayed on the remote controller display.
The set temperature and airflow rate are memorized in the remote controller. When the
remote controller is reset due to replacement of battery, it is necessary to set the
temperature and airflow rate again for HOME LEAVE operation.
The operation mode cannot be changed while HOME LEAVE operation is being used.
Dry rotating speed + A rpm
Same as cooling / heating in
= 50 rpm
Target temp.
18˚C
POWERFUL
ON
POWERFUL
OFF
Fan
A rpm
H tap
Set tap
Airflow rate
Temperature
or
as you like.
Fan speed
H tap + A rpm
H tap + A rpm
H tap + A rpm
POWERFUL operation
It should be the lower limit of
cooling temperature.
20 minutes
Selectable range
Airflow rate
18 ~ 32°C
5 steps,
10 ~ 30°C
5 steps,
Target temperature
18°C
Lowered by 2.5°C
30°C
The target temperature is
kept unchanged.
It counts 20 minutes also
in the remote controller.
Ending condition:
1. After the lapse of 20 minutes.
2. Operation OFF
3. POWERFUL operation is OFF.
Main Functions
,
,
(R19177)
37