Daikin FLKS25BAVMB Service Manual page 85

Inverter pair floor / ceiling suspended dual type flk(x)s-ba series
Hide thumbs Also See for FLKS25BAVMB:
Table of Contents

Advertisement

SiBE05-722EE
Troubleshooting
Check No.11
Refer to P.103
Check the indoor unit - outdoor
unit connection wires.
Check the voltage of the
connection wires on the indoor
terminal board between No. 1
and No. 3, and between No. 2
and No. 3.
Check the LED A on the outdoor
unit PCB.
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the power supply voltage.
Is the
voltage fluctuation
within ±10% from the
rated value?
YES
Is there any wiring error?
NO
Properly insulated?
YES
Is LED A blinking?
Blink
Rotate the
outdoor fan by hand.
Does the outdoor fan rotate
smoothly?
YES
Check No.11
Check the power supply
waveform.
Is there any disturbance?
YES
NO
YES
NO
Continuously ON or OFF
NO
NO
Troubleshooting
Correct the power supply.
Correct the indoor unit -
outdoor unit connection wires.
Replace the connection wires
between the indoor unit and
outdoor unit.
Replace the outdoor unit PCB
(main PCB).
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Replace the indoor unit PCB
(control PCB).
Locate the cause of the
disturbance of the power
supply waveform, and correct
it.
(R22596)
75