Configuration; Making Field Settings; About Making Field Settings; Field Setting Components - Daikin RWEYQ8T9Y1B Installation And Operation Manual

Vrv iv water-cooled system air conditioner
Table of Contents

Advertisement

1 2 3 4 5 6 7 8 9 10
+
X3M
X2M
a
Relay (normally closed) (field supply)
b
Flow switch (field supply)
Multifunction outputs
To monitor the outdoor unit operation or trigger field supplied
equipment connected to the outdoor unit, this RWEYQ*T9, series is
equipped with 5 output contacts.
General contact specifications: 220 V AC, 3 mA-0.5 mA.
To connect these output signals, choose the applicable contacts in
the X3M terminal in the table below:
a
b
c
d
X3M
e
Terminal
Function
a
Error on remote controller
b
Compressor operation
c
Heating operation
d
Cooling operation
e
Water pump operation request
6

Configuration

INFORMATION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
DANGER: RISK OF ELECTROCUTION
6.1

Making field settings

6.1.1

About making field settings

To continue the configuration of the VRV IV heat recovery system, it
is required to give some input to the PCB of the unit. This chapter
will describe how manual input is possible by operating the push
buttons on the PCB and reading the feedback from the 7‑segment
displays.
Making settings is done via the master outdoor unit.
RWEYQ8~14T9V1B+RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452190-1A – 2017.04
X2M
0
-
TW1
TW2
10
IN
OUT
b
X3M
a
YLW
a
ORG
RED
b
BRN
BLU
c
BLU
WHT
d
WHT
BLK
e
BLK
X3M
YLW
ORG
RED
BRN
BLU
BLU
WHT
WHT
BLK
BLK
Next to making field settings it is also possible to confirm the current
operation parameters of the unit.
Push buttons
Performing special actions (automatic refrigerant charge, test run,
etc.) and making field settings (demand operation, low noise, etc.)
happens by way of operating the push buttons.
See also:
"6.1.2 Field setting components" on page 23
"6.1.3 To access the field setting components" on page 24
PC configurator
For VRV IV heat recovery system it is alternatively possible to make
several commissioning field settings through a personal computer
interface (for this, option EKPCCAB is required). The installer can
prepare the configuration (off-site) on PC and afterwards upload the
configuration to the system.
See also:
"6.1.9  To connect the PC configurator to the outdoor
unit" on
page 26.
Mode 1 and 2
Mode
Mode 1
Mode 1 can be used to monitor the current
situation of the outdoor unit. Some field setting
(monitoring
contents can be monitored as well.
settings)
Mode 2
Mode 2 is used to change the field settings of
the system. Consulting the current field setting
(field settings)
value and changing the current field setting
value is possible.
In general, normal operation can be resumed
without special intervention after changing field
settings.
Some field settings are used for special
operation (e.g., 1 time operation, recovery/
vacuuming setting, manual adding refrigerant
setting, etc.). In such a case, it is required to
abort the special operation before normal
operation can restart. It will be indicated in
below explanations.
See also:
"6.1.4 To access mode 1 or 2" on page 24
"6.1.5 To use mode 1" on page 24
"6.1.6 To use mode 2" on page 24
"6.1.7 Mode 1: Monitoring settings" on page 25
"6.1.8 Mode 2: Field settings" on page 25
6.1.2

Field setting components

Location of the 7‑segment displays, buttons and DIP switches:
a
b
DS1 DS2
BS1 BS2
BS3
X27A
BS1
MODE: For changing the set mode
BS2
SET: For field setting
BS3
RETURN: For field setting
DS1, DS2
DIP switches
a
7‑segment displays
b
Push buttons
6 Configuration
Description
Installation and operation manual