Faul
t
Fault Description
cod
e
6
Motor blockage protection
The communication fault
7
between the indoor unit and
outdoor unit
8
Phase current imbalance
9
U phase current fault
10
V phase current fault
ON/OFF UNITARY AIR CONDITIONER TECHNICAL& SERVICE MANUAL V6.0
O
T
I
N
G
O
T
I
N
G
Possible Reason of Abnormality
1.Outdoor ambient temperature sensor fault;
2. Outdoor coil temperature sensor fault;
3.Outdoor control board fault.
1.The connection cable connect wrong
between the indoor unit and outdoor unit;
2.The communication cable connect loose;
3.The communication cable is fault;
4.The indoor control board is fault;
5.The outdoor control board is
fault;
6.Communication circuit fuse open;
7.The specification of communication cable is
incorrect.
1.The supply voltage fluctuates more than
4%;
2.The compressor power cord connect loose;
3.The AC contactor is fault;
4.The compressor motor fault.
1.Compressor U phase power cord is fault or
connect wrong;
2.Outdoor control board is fault;
3.The Compressor is fault
1.Compressor V phase power cord is fault or
connect wrong;
2.The outdoor control board is fault;
3.The compressor is fault
How to Deal With
1.Replace outdoor ambient
temperature sensor;
2.Replace outdoor coil temperature
sensor;
3.Replace Outdoor control board.
1.Reconnect the connection cable refer
to the wiring diagram;
2.Reconnect the communication cable;
3.Replace the communication cable;
4.Replace the indoor control board;
5.Replace the outdoor control board;
6.Check the communication circuit,
adjust the DIP switch and the
short-circuit fuse.
7.Choose suitable communication
cable refer to the user manual
1.Normally protection;
2.Reconnect the wire refer to thewiring
diagram;
3.Replace the AC contactor;
4.Replace the compressor.
1.Replace the U phase power cord or
reconnect the U phase power cord
refer to the wiring diagram;
2.Replace the outdoor control board;
3.Replace the compressor.
1.Replace the V phase power cord or
reconnect the V phase power cord refer
to the wiring diagram;
2.Replace the outdoor control board;
3.Replace the compressor.
REMARKS
Applied to
ON/OFF
air-condition
ers with 2
control
boards
Application
of
three-phase
power
supply
models
Application
of
three-phase
power
supply
models
Application
of
three-phase
power
supply
models
96