Combustion And Ignition System Description - Keison PFP7 Operating And Service Manual

Flame photometer
Table of Contents

Advertisement

8.2

Combustion and ignition system description

Air at 14 to 30 psi,
Air at 14 to 30 psi,
6 litres/min
6 litres/min
Rear panel
Rear panel
Fuel gas regulated
Fuel gas regulated
to less than 0.5 psi
to less than 0.5 psi
Figure 8.2.1: Combustion and ignition system
The PFP7 can be used with propane, butane, natural gas or L.P.G. at pressures as defined in
Section 2. Immediately behind the rear panel fuel bulkhead is the fuel solenoid valve. This
solenoid valve is normally closed when there is no power to the instrument or where there is
power to the instrument but the flame is not alight. The solenoid will be latched in the open
position when the flame is alight and has been detected by the flame thermocouple. The fuel
solenoid can be held open manually during the flame ignition sequence by holding down the
front panel ignition switch; fuel then flows through small bore copper tubing to the fuel valve on
the front panel. This is a very fine needle valve and to avoid damage, this control should never
be screwed hard fully clockwise and should not be used as an on/off valve. From the fuel valve
the gas then passes to the mixing chamber and then on to the burner. A restrictor screw is fitted
to the mixing chamber fuel inlet for use with propane, butane or L.P.G. but must be removed if
natural gas is used.
Air is fed through the rear panel to the air regulator. The air regulator is factory set to 12psi.
Adjustment should not be necessary but can be achieved by lifting the yellow locking ring and
rotating the knob on the side of the regulator until the correct pressure is shown on the pressure
gauge. From the air regulator the air passes to the nebuliser where it acts as an atomising
agent.
Ignition is achieved by passing a high voltage spark between the ignition electrode and the
centre of the burner. The spark is generated by the self-contained ignition unit mounted inside
the instrument. This is activated by depressing the front panel ignition switch, which
simultaneously opens the fuel solenoid, allowing gas to flow through the stream of sparks and
hence ignite. The ignition switch must be manually held down until the thermocouple, mounted
at the top of the back of the chimney, detects the temperature rise due to the flame, latches the
solenoid in the open state and energises the FLM indicator in the display window. If the fuel flow
ceases and the flame is extinguished, the thermocouple will detect the fall in temperature and
the solenoid will automatically be closed, stopping any further gas escaping to atmosphere.
Regulator & gauge
Regulator & gauge
assembly
assembly
Solenoid
Solenoid
Ignition switch
Ignition switch
& flame
& flame
detect circuits
detect circuits
29
To nebuliser
To nebuliser
Needle valve
Needle valve
(fuel)
(fuel)
To 'Fuel in' on
To 'Fuel in' on
mixing chamber
mixing chamber
PFP7/REV C/01-08

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pfp7/c

Table of Contents