Facing Requirements - FireplaceXtrordinair 42 Apex Clean Face Installation Manual

Wood-burning zero-clearance fireplace
Hide thumbs Also See for 42 Apex Clean Face:
Table of Contents

Advertisement

44

Facing Requirements

The fireplace requires non-combustible facing (typically 1/2" thick concrete-board) from the base of
the fireplace to the framing header (min. 78-1/2""). The non-combustible facing must extend to the
framing members on both sides of the fireplace. Do not use drywall or other combustible in this area
(see illustration below).
The non-combustible facing must have an opening for the convection air outlet (see illustration
below).
The non-combustible facing may be attached to the front of the fireplace and non-combustible
framing with screws. Do not penetrate the fireplace more than 3/4".
Facing over 1" thick (brick, thick marble) may be used around the perimeter of the faceplate.
NOTE: leave a minimum of 1/8" between the top of the face and the surrounding facing material to
accommodate removal of the face.
Drywall
(or other combustible)
© Travis Industries
Installation
(for qualified installers only)
Minimum 42"
8/25/2017 - 1450
Framing Header
Convection Air Outlet
(from upper manifold)
(use included trim if desired)
Non-Combustible Facing
(cement board, tile, marble, etc.)
Non-Combustible Framing
(included with fireplace)
The facing will need to be
notched to go around the
bypass rod.
42 Apex CF