Setting Saturation Limits; Setting Process Alarms Limits; Managing Process Alarms Settings - ABB LLT100 Operating Instructions Manual

Laser level transmitter oi-llt100-en rev. d
Hide thumbs Also See for LLT100:
Table of Contents

Advertisement

LLT100
Laser level transmitter

10.3 Setting saturation limits

If the PV is below the lower range value (LRV), the signal is
driven to the "Low Saturation" limit. If the PV is above the
upper range value (URV), the signal is driven to the "High
Saturation" limit.
To set a saturation limit:
1. From the Process Alarm menu, select Saturation Limits >
Low (or High) Saturation.
2. In the resulting menu, edit the mA value and press OK.

10.4 Setting process alarms limits

In the Process Alarm Limits menu, you can configure the exact
value to which the signal can be driven.
To avoid problems, the "Low Alarm" value must be lower than
the "Low Saturation" limit, and the "High Alarm" value must be
higher than the "High Saturation" limit.
10.4.1 Setting current out alarms
The low alarm value range is between 3.6  mA and 3.8  mA
(default: 3.6  mA). The high alarm value range is between
20.5  mA and 22 mA (default: 21  mA). Current alarms are
alarms sent when the instrument itself has become unreliable
due, most of the time, to hardware failure.
To set the Current Out alarm limits:
1. From the Process Alarm menu, select Process Alarm
Limits > Current Out > Low Alarm or High Alarm.
2. From there, edit the value as necessary, based on the
information above.
3. Press OK.
10.4.2 Setting level and ullage alarms
These alarms are only set for HART communication purposes.
To better understand the meaning of each alarm limit
(Low Low, Low, High, High High), see Figure 20 "Limits
variables diagram" on page 29.
To set a level or ullage alarm:
1. From the Process Alarm menu, select Process Alarm
Limits > Level or UIlage and the alarm level that you want
to configure (Low Low, Low, High, High High).
2. Edit the level as necessary.
Figure 20 illustrates that the Low Low value must be lower
than the Low value, and that the High High value must be
higher than the High value. The LLT100 will not allow you to
enter values that do not meet this criteria.
30 User Guide | OI-LLT100-EN Rev. D
10.4.3 Enabling level and ullage alarms
WIth the LLT100, you can define alarms and activate them
later on.
To do so:
1. From the Process Alarm menu, select Process Alarm
Limits > Level or Ullage.
2. From the Level or Ullage menu, select Enable.
3. From the Enable menu, select Enabled and press OK.

10.5 Managing process alarms settings

Once you have completed setting up your process alarms, you
can save that setup or go back to factory settings if you prefer.
10.5.1 Saving settings as default
To save process alarms settings:
1. From the Process alarm menu, select Settings > Save as
default.
2. From the Save as default screen, press OK.
The settings saved become the default configuration.
10.5.2 Resetting to default values
If you modified the process settings and realize that your
configuration should not be saved, it is possible to revert the
default display settings.
To revert to the default display settings:
1. From the Process alarm menu, select Settings > Reset to
default.
2. From the Reset to default screen, press OK.
The settings go back to their default value.
10.5.3 Resetting to factory values
To revert to the process alarms settings that came with your
instrument directly from the factory:
1. From the Process Alarm menu, select Settings > Reset to
factory.
2. From the Reset to factory screen, press OK.
The settings revert to the ones that came with the unit
directly from the factory.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents