The sequence of pulses issued by the control box identifies the possible types of malfunction, which are
listed in the table below.
SIGNAL
2 pulses
3 pulses
4 pulses
7 pulses
10 pulses
5.

MAINTENANCE

The burner requires periodic maintenance carried out by a qualified and authorised technician in conformity
with legislation and local standards.
Maintenance is essential for the reliability of the burner, avoiding the excessive consumption of fuel and
consequent pollution.
Before carrying out any cleaning or control always first switch off the electrical supply to the
burner acting on the main switch of the system.
THE BASIC CHECKS ARE:
Leave the burner working without interruption for 10 min., checking the right settings of all the components
stated in this manual. Then carry out a combustion check verifying:
CO
( %) content
2
6.

FAULTS / SOLUTIONS

Here below you can find some causes and the possible solutions for some problems that could cause a fail-
ure to start or a bad working of the burner. A fault usually makes the lock-out lamp light which is situated
inside the reset button of the control box (9, fig. 1, page 1).
When lock out lamp lights the burner will attempt to light only after pushing the reset button. After this if the
burner functions correctly, the lock-out can be attributed to a temporary fault.
If however the lock out continues the cause must be determined and the solution found.
2754
The flame does not stabilise at the end of the safety time:
– faulty ionisation probe;
– faulty or soiled gas valves;
– neutral/phase exchange;
– faulty ignition transformer
– poor burner regulation (insufficient gas).
Minimum air pressure switch does not close:
– make sure VPS trips to produce lockout;
– air pressure switch faulty;
– air pressure switch incorrectly regulated;
– fan motor does not run;
– maximum air pressure switch operating.
Min. air pressure switch does not open or light in the chamber before firing:
– air pressure switch faulty;
– air pressure switch incorrectly regulated.
Loss of flame during operations:
– poor burner regulation (insufficient gas);
– faulty or soiled gas valves;
– short circuit between ionisation probe and earth.
– Wiring error or internal fault.
Smoke temperature at the chimney
PROBABLE CAUSE
CO content (ppm).