Daikin RTSYQ10PY1 Installation Manual page 27

Vrv iii-c system air conditioner
Table of Contents

Advertisement

3.
Calculating the refrigerant density using the results of the calcu-
lations in steps 1 and 2 above.
total volume of refrigerant in the
refrigerant system
3
size (m
) of smallest room in which
there is an indoor unit installed
If the result of the above calculation exceeds the maximum con-
centration level then make similar calculations for the second then
third smallest room and so until the result falls short of the maxi-
mum concentration.
4.
Dealing with the situations where the result exceeds the maxi-
mum concentration level.
Where the installation of a facility results in a concentration in
excess of the maximum concentration level then it will be neces-
sary to revise the system. Please consult your Daikin supplier.