Delta Electronics 7KVA User Manual page 17

J-series 11kva (1:1),11kva (3:1)
Table of Contents

Advertisement

INPUT AND OUTPUT CONNECTION:
When connecting the cable, please notice that:
1. Before connecting, turn off the UPS and cut off not merely the AC source but also the battery.
2. Ensure the cable is fitted. The minimum tightening torque shall not be less than 35 lbs with a cable sleeve & secured by the
connector clamp.
3. Connect the EARTH wire to the terminal marked with " G " .
The connective methods of input and output:
(A) Europe model
O U T P U T
G
OUTPUT
L
200Vac
208Vac
220Vac
230Vac
240Vac
N 1
L
N
200Vac
208Vac
220Vac
230Vac
240Vac
5KVA/ 7 KVA/ 9 KVA/ 11 KVA
INPUT
N
N
11KVA (3:1)
SHEET 17 TO 18
IN P U T
L 1
L 2
R e c tifire In p u t
Bypass input
T
S
R
Rectifire Input
Bypass input
15
Connect to
G
EARTH
Connect to
R
EARTH