Replace Modules, Fan Trays, and Power Supplies

Replace NCS 55A1-24H, NCS 55A1-36H-S, NCS 5501 and NCS
5501-SE Fan Modules
The fan module is designed to be removed and replaced while the system is operating without presenting an
electrical hazard or damage to the system, if the replacement is performed within 2 minutes.
The NCS 5501 and NCS 5501-SE routers support NCS-1RU-FAN-FW (port-side intake airflow) and
Note
NCS-1RU-FAN-RV (port-side exhaust airflow) fan modules.
The NCS 55A1-24H, NCS 55A1-36H-S routers support NC55-A1-FAN-FW (port-side intake airflow)
and NC55-A1-FAN-RV (port-side exhaust airflow) fan modules.
The airflow direction must be the same for all power supply and fan modules in the chassis.
Note
Step 1
To remove a fan module, follow these steps:
a) Press two latches on the fan module, grasp the handle of fan module.
Replace NCS 55A1-24H, NCS 55A1-36H-S, NCS 5501 and NCS 5501-SE Fan Modules, page 53
Replace NCS 5502 and NCS 5502 SE Fans, page 55
Replace Power Supply, page 56