This current probe has been designed for non intrusive, accurate measurements of small
AC currents. Using the latest technologies (internal memory for calibration data) provides
current ranges from 0.2 A up to 200 A. The measurement range can be selected in the PQ
Analyze software: IAC20 or IAC200.
To protect against electrical shock:
Electrical Characteristics
Nominal current In:
Measuring ranges:
Crest factor:
Peak current:
Max. non destructive current:
Conductor position influence:
Error due to adjacent conductor:
Phase error (to reference conditions):
Frequency (clamp without the
instrument):
Temperature coefficient:
Safety:
General Characteristics
Maximum conductor size:
Cable length:
Operating temperature range:
Storage temperature range:
Operating humidity:
Weight (per clamp):
Order-number:
Reference Conditions
Environment temperature range: +18 °C to +26 °C.
Humidity:
6-14
Utilize the clamps only on insulated conductors, max.
600 V rms or dc to ground.
Use personal protective equipment measures as required
by local government agencies, when attaching clamps to
live circuits.
XW Warning
20 A, 200 A AC rms
0.2 A – 20 A or 2 A – 200 A
< 3
74 A, 300 A
Up to 300 A rms
< 0.5 % of range for 50/60 Hz
≤15 mA/A for 50 Hz
< ±0.5 degrees
40 Hz – 10 kHz (−3 dB)
0.015 % of range/ °C
300 V CAT IV, type C sensor, pollution
degree 2
Diameter: 15 mm
Bus bar: 15 x 17 mm
2 m
−10 °C - +55 °C
−20 - +70 °C
15 % - 85 % (non-condensing)
Approx. 220 g
2540450
20 up to 75 % r.h.