Fluke 1760 User Manual page 77

Power quality recorder
Hide thumbs Also See for 1760:
Table of Contents

Advertisement

Harmonics Range
Intrinsic uncertainty
basic aggregation interval 200 ms
Interharmonics Range
Intrinsic uncertainty
basic aggregation interval 200 ms
Conditions for Harmonics and
Interharmonics Specifications
Temperature
Humidity
Supply voltage
Common mode interference voltage
Static electricity discharge
Radiated electric fields
Voltage unbalance – Range
Intrinsic uncertainty
Flicker
All PQ parameters are evaluated in accordance with IEC 61000-4-30 Class A, 2008 Edition 2
In regulations the standard expression for V
Number of inputs
Sensor safety
Basic unit safety rating
Nominal voltage (rms)
Range (peak value)
Overload capacity (rms)
Voltage rise rate
Input resistance
Input capacitance
Input filter
<25 % of VRMS fundamental up to a THD of 50 %
≥1 % Vnom: ±5 % of reading
< 1 % of Vnom: ±0.05 % of Vnom
as per IEC 61000-4-7:2002 and amendment 1:2008, IEC
61000-2-4 Class 3
<25 % of VRMS fundamental up to a TID of 50 %
≥1 % Vnom: ±5 % of reading
< 1 % of Vnom: ±0.05 % of Vnom
as per IEC 61000-4-7:2002 and amendment 1:2008
within operating temperature range
10%-60% r.H.
83 - 264 V ac, 45 - 65 Hz, 100 - 375 V dc
≤ Vnom
IEC 61326-1 / industrial environment
IEC 61326-1 / industrial environment
0 to 100 %
±0.15 % absolute deviation
as per EN 61000-4-15:2003:
10 min (Pst), 2 h (Plt)
is U
nom
nom
Measurement inputs
8 galvanically isolated inputs for voltage and current
measurements.
up to 600 V CAT IV depending on sensor
300 V CAT III
100 mV
280 mV
1000 V, continuously
max. 15 kV / μs
1 M Ω for instrument, 1000 V sensor 10 MΩ
< 50 pF
Each channel is equipped with a passive low-pass filter, an anti-
aliasing filter and a 16-bit A/D converter. All channels are sampled
synchronously with a common quartz-controlled clock pulse.
The filters protect against voltage transients and limit the signal rise
rate, reduce high frequency components and especially the noise
voltage above half the sampling rate of the A/D converter by 80 dB,
thus achieving very small measuring errors in an exceptionally large
amplitude range. This is also valid under extreme operating
conditions like transient voltages at the output of converters.
Specifications
General Specifications
5
5-5